beautypg.com

Locating the new water heater (cont’d) – State GS6 65 XRRT User Manual

Page 8

background image

Combustion Air and Ventilation

for Appliances Located in

Unconfined Spaces

Unconfined Space is a space whose volume is not less than 50

cubic feet per 1,000 Btu per hour of the aggregate input rating

of all appliances installed in that space. Rooms communicating

directly with the space in which the appliances are installed,

through openings not furnished with doors, are considered a

part of the unconfined space

In unconfined spaces in buildings, infiltration may be adequate

to provide air for combustion, ventilation and dilution of flue

gases. However, in buildings of tight construction (for example,

weather stripping, heavily insulated, caulked, vapor barrier,

etc.), additional air may need to be provided using the methods

described in Combustion Air and Ventilation for Appliances

Located in Confined Spaces.

Combustion Air and Ventilation

for Appliances Located in

Confined Spaces

Confined Space is a space whose volume is less than 50 cubic

feet per 1,000 Btu per hour of the aggregate input rating of all

appliances installed in that space.

a. ALL AIR FROM INSIDE BUILDINGS:

(See Page 7 Figure 1, and Figure 2 below)

The confined space shall be provided with two permanent

openings communicating directly with an additional room(s)

of sufficient volume so that the combined volume of all

spaces meets the criteria for an unconfined space. The total

input of all gas utilization equipment installed in the com-

bined space shall be considered in making this determina-

tion. Each opening shall have a minimum free area of one

square inch per 1,000 Btu per hour of the total input rating

of all gas utilization equipment in the confined space, but

not less than 100 square inches. One opening shall com-

mence within 12 inches of the top and one commencing

within 12 inches of the bottom of the enclosure.

b. ALL AIR FROM OUTDOORS: (see Figures 3-5)

The confined space shall be provided with two permanent

openings, one commencing within 12 inches of the top

and one commencing within 12 inches from the bottom

of the enclosure. The openings shall communicate direct-

ly, or by ducts, with the outdoors or spaces (crawl or attic)

that freely communicate with the outdoors.

1. When directly communicating with the outdoors, each

opening shall have a minimum free area of 1 square inch

per 4,000 Btu per hour of total input rating of all equip-

ment in the enclosure. (See Figure 3.)

2. When communicating with the outdoors through vertical

ducts, each opening shall have a minimum free area of 1

square inch per 4,000 Btu per hour of total input rating of

all equipment in the enclosure. (See Figure 4.)

3. When communicating with the outdoors through horizon-

tal ducts, each opening shall have a minimum free area of

1 square inch per 2,000 Btu per hour of total input rating

of all equipment in the enclosure. (See Figure 5.)

4. When ducts are used, they shall be of the same cross-sec-

tional area as the free area of the openings to which they

connect. The minimum short side dimension of rectangu-

lar air ducts shall not be less than 3 inches. (See Figure 5.)

5. Louvers and Grilles: In calculating free area, consideration

shall be given to the blocking effect of louvers, grilles or

screens protecting openings. Screens used shall not be

smaller than

1

4

inch mesh. If the free area through a design

of louver or grille is known, it should be used in calculat-

ing the size opening required to provide the free area

specified. If the design and free area is not known, it may

be assumed that wood louvers will be 20-25 percent free

area and metal louvers and grilles will have 60-75 percent

free area. Louvers and grilles shall be fixed in the open

position or interlocked with the equipment so that they are

opened automatically during equipment operation.

6. Special Conditions Created by Mechanical Exhausting or

Fireplaces: Operation of exhaust fans, ventilation systems,

clothes dryers or fireplaces may create conditions requir-

ing special attention to avoid unsatisfactory operation of

installed gas utilization equipment.

Locating the New Water Heater (cont’d)

Figure 2

Figure 4

Figure 5

Figure 3

8