Required breaker settings, Input and upstream breakers — minimum settings, Output and downstream breakers — minimum settings – American Power Conversion Symmetra MW User Manual
Page 39

Symmetra MW 1000 kW 480 V Installation - 990-4112E
35
Required Breaker Settings
The Symmetra
®
MW is a fault-tolerant system capable of handling and surviving overloads and
internal/external faults. The overload performances and fault clearings are possible when the system
meets specified minimum requirements for breaker settings. The settings are specified in the tables
below, but some of them can also be found in the Electrical Specification section. The settings are all
minimum settings and may not result in a drop-out.
Input and upstream breakers — minimum settings
Output and downstream breakers — minimum settings
See also
See separate guide on parallel operation for information on required breaker settings in
parallel systems.
Q1, Q5, and any upstream breaker
Duration [S]
Current [A]
Total load [%]
Event/Operation
< 0.005
18 kA
--
Internal fault clearing
1880*
130
Overload on-line
1245
100
On-line
1370
110
On-line + Max. Battery
Charge
* Only applicable to Q1
∞
∞
∞
Q2, Q4, Q6, and any downstream breaker
Duration [S]
Current [A]
Total load [%]
Event/Operation
< 0.005
18 kA
--
Internal fault clearing.
60
2406*
200
Overload on-line
600
1504*
125
Overload on-line
1203
100
On-line
* Only applicable to Q2 and Q4
∞