Symmetra MW 1000 kW 480 V Installation - 990-4112E

29

Electrical Specification

Installation Planning Data

Note

The installation is a typical installation including ancillary equipment, which is available
from APC.

Note

UPS and External Bypass Static Switch feed must be generated from synchronized
sources.

WARNING!
Supply the UPS from a dedicated, grounded 3-wire Wye service.

WARNING!
The UPS has no internal manual disconnect devices to switch off external AC (Q1
and Q5) and DC (Q7 and Q8) input power. Ensure that disconnection devices are
available as separate components for this installation.

CAUTION!
Ensure clockwise phase rotation (L1, L2, L3) of input voltages.

Q5

Q3

Q1

Q2

Optional

Q6

Optional

Q4

Optional

Q7

Q8

Service (480V 3-phase,
3- wire grounded Wye)

Output (480V 3-phase,
3-wire only)

Maintenance Bypass Panel

External Bypass SSW

UPS

Battery
Breaker 1

Battery
Breaker 2