Electrical Installation: Relay Board (Optional)
Symmetra MW 1000 kW 480 V Installation - 990-4112E
25
K11
Bypass operation
• UPS is running in normal operation/
bypass operation according to AS400/
Novell.
Active on
Opr. mode
K12
Maintenance bypass ON
• The maintenance bypass switch is active.
Active on
Opr. mode
K13
Stand-by operation
• UPS is in stand-by operation.
Active on
Opr. mode
K14
Boost charge operation
• UPS is boost charging the batteries.
Active on
Opr. mode
K15
Fan fault
• Blocked or faulty fan.
Fail safe
Fault
K16
High equipment
temperature or inverter
fuse blown
• Static Switch temperature is high;
• Main Inverter failure (high temperature
or blown fuse);
• Delta Inverter temperature is high;
• Magnetics temperature is high;
• Isolation Transformer temperature is high
(optional);
• Battery temperature is high.
Fail safe
Warning
IN1
Generator active
• System on generator
System is
running on
generator.
Battery
charging is
derated.
IN2
Battery room ventilation
fault
• Battery room ventilation
Ventilation
fault in
battery
room.
Battery
charging is
off.
IN3 -
IN8
Reserved for future use
Relay
ID
Name
Events that will trigger the alarm
Mode
Comment