beautypg.com

Personal safety, Inverter safety, Important safety instructions – Outback Power Systems GFX International Series Installation Manual User Manual

Page 5

background image

Important Safety Instructions

900-0111-01-00 Rev B

3

CAUTION: Equipment Damage

Only use components or accessories recommended or sold by OutBack Power
Technologies or its authorized agents.

IMPORTANT:

Do not attempt to install this equipment if it appears to be damaged in any way. See
the Warranty section for instructions on returning the equipment.

Personal Safety

WARNING: Personal Injury

¾ This equipment weighs in excess of 22 kg (49 lb). Use safe lifting techniques when

lifting this equipment as prescribed by local codes.

¾ Use standard safety equipment such as safety glasses, ear protection, steel-toed

safety boots, safety hard hats, etc., as prescribed by local codes when working on
this equipment.

¾ Use standard safety practices when working with electrical equipment. (Remove all

jewelry, use insulated tools, wear cotton clothing, etc.)

¾ Never work alone when installing or servicing this equipment. Have someone

nearby that can assist if necessary.

Inverter Safety

WARNING: Lethal Voltage

¾ Review the system configuration to identify all possible sources of energy. Ensure

ALL sources of power are disconnected before performing any installation or
maintenance on this equipment. Confirm that the terminals are de-energized
using a validated voltmeter (rated for a minimum 1000 Vac and 1000 Vdc) to verify
the de-energized condition.

¾ Do not perform any servicing other than that specified in the installation

instructions unless qualified to do so, or have been instructed to do so by OutBack
Power Technologies Technical Support personnel.

WARNING: Burn Hazard

Internal parts can become hot during operation. Do not remove the cover during
operation or touch any internal parts. Be sure to allow sufficient time for internal parts
to cool down before attempting to perform any maintenance.

WARNING: Fire Hazard

¾ Do not place combustible or flammable materials within 3.7 m (12 feet) of

the equipment.

¾ This product contains relays with moving parts and is not ignition-protected.
¾ Ensure AC, DC, and ground cable sizes conform to local codes. See pages 18

through 21 for minimum size requirements. Ensure all conductors are in good
condition. Do not operate the unit with damaged or substandard cabling.