Specifications

900-0114-01-00 Rev A

51

Table 19 48-Volt Inverter Settings

48 Vdc Inverter

Default

Minimum

Maximum

Stacking

Stack Phase

Master

Master,Classic Slave, OB Slave L1, 3p Classic B,

or 3p Classic C

Power Save Level

Master Adjust Only

0 0 7

Slave Adjust Only

1 1 15

Sell

Sell RE Volts

52 Vdc

40 Vdc

60 vdc

Grid Tie Window

User

IEEE or User

Grid Tie Authority

GridTie

GridTie or No Sell

Calibration (Cal)

Vac Input Adjustment1

236 220 254

Vac Output Adjustment1

236 220 254

Battery Vdc Adjustment2

2 0 4

1These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower

voltages. One count equals approximately 1 Vac. The range of adjustment is 15 Vac above nominal, and 17 Vac
below nominal.

2

These values are in digital counts, not volts. One count equals 0.4 Vdc. The range of adjustment is 0.8 Vdc above or

below nominal.