Operation

12

900-0114-01-00 Rev A

STATUS LEDS

GREEN

Solid: The inverter is ON and providing power. If accompanied by solid yellow LED, unit is selling power to

the utility grid. (See page 23 for a description of the Sell function.)

Flashing: The inverter has been turned ON but is idle. May be accompanied by the yellow LED. If not

accompanied by the yellow LED, the unit in inverting mode and is idle due to lack of demand. This can be
because the unit is in Search mode. (See page 14 for a description of Search.)

Off: Unit is OFF. It is not waiting to provide power. Any power present is from another source such as the

utility grid or generator. (See Startup on page 9, or the system display manual, to turn the unit ON.) The
unit may also be a slave that is in Power Save mode. If so, the master inverter may still be providing power
to the system. (See page 27 for a description of Power Save.)

YELLOW

Solid: The AC source is connected and providing power. Unit may or may not be charging the batteries,

depending on settings. May be accompanied by green LED.

Flashing: The AC source is present but has not been accepted. If flashing continues, the unit is refusing the

source. This can occur for the following reasons.

 The AC source may have quality issues. External diagnosis may be required. (See page 15 for a

description of input criteria. See the system display manual for diagnosis using the meter displays.)

 In the MATE system display, the AC Input Control menu is set to DROP. (See the MATE manual for a

description of the AC IN hot key.)

 In the MATE, the HBX feature or the Grid Use feature intentionally disconnected the inverter. (See the

MATE manual for a description of these modes.)

Off: No AC source is detected. If a source is supposed to be present, confirm the voltage between AC HOT

IN and AC NEUTRAL IN terminals.

RED

Solid: ERROR. Unit has shut down due to a critical problem which may be internal or external to the

inverter. This LED is accompanied by an Error message in the system display. See page 36 for a
description of ERROR messages.

Flashing: WARNING. Unit has detected a non-critical problem but has not yet shut down. A Warning does

not always lead to a shutdown — if it does, it becomes an Error. This LED is accompanied by a Warning
message in the system display. See page 37 for a description of Warning messages.

Off: No problems are detected.

Table 3

Status LED Quick Reference

Color State

Inverter

State

Notes

Solid GREEN

Inverter is ON and providing power.

If accompanied by YELLOW LED, unit is selling.

Flashing GREEN

Inverter is ON but standing by.

Unit may be in Search mode.

GREEN

Off

Inverter is not providing power.

Unit is either OFF or has been replaced by AC
source (see next item).

Solid YELLOW

AC source connected and providing
power.

Unit may or may not be charging batteries,
depending on settings.

Flashing YELLOW

AC source present but not yet accepted. Unit may be programmed not to accept the

source, or the source may have quality issues.

YELLOW

Off

No AC source is detected.

If source is present, check AC input.

Solid RED

ERROR. Unit has shut down. See
Troubleshooting.

To see Error messages, see the system display
manual.

Flashing RED

WARNING. Unit detected a problem but
has not yet shut down. See
Troubleshooting.

To see Warning messages, see the system
display manual.

RED

Off

No problems detected.