Table 4 Basic Troubleshooting Steps
Symptom Unusual LEDs
Possible Cause
Possible Remedy
No AC IN LED
No AC input.
See “Will not connect to AC” category
below.
Will not charge.
AC IN LED normal
Charger set to OFF.
MATE system display only: Check
Charger Control screen with AC IN hot
key and set to ON or AUTO. (If this
setting was intentional, then no action is
required.)
AC IN LED normal
Charge complete or nearly
complete.
Check the DC voltage and charging
stage using the system display, if
present. Confirm with DC voltmeter.
AC IN LED normal
System display’s DC meter reads
significantly higher than actual
battery voltage.
Check the DC voltage on the inverter’s
DC terminals. If different from the
system display reading, the inverter
could be damaged. Otherwise, check
the DC voltage on batteries with a
voltmeter. If different from the reading
on the inverter, this could be a DC
connection problem.
AC IN LED normal
Generator type does not work well
in conjunction with Grid/Generator
Support feature (see page 16).
MATE system display only: Turn off the
ac2/gen support feature in
ADV/FX/GEN menu. The ac transfer
control must be set to gen in order to
do this. In current models, if ac transfer
control is set to grid, the support
feature cannot be disabled.
Low charge
rate.
AC IN LED normal
High output loads. If total loads and
charge exceed input setting, charge
will decrease to give priority to
loads.
Turn off some of the output loads and
test the charge rate again.
None (AC IN LED is
illuminated)
Inverter priority
MATE system display only: Check Stop
Sell Reasons menu (STATUS/FX/SELL).
The inverter may be behaving correctly.
None (AC IN LED is
illuminated)
AC source does not meet
requirements.
Verify grid voltage and frequency.
Determine if they are within the
inverter’s approved limits. If not, the
inverter is behaving correctly. Contact
the utility company if necessary.
MATE system display only: The program
selections for limits are IEEE or USER.
None (AC IN LED and
Inverter are illuminated)
High output loads will consume
power before it is returned to the
utility grid.
Turn off some output loads and observe
the sell function.
Will not sell
power to the
utility grid.
None (AC IN LED is
illuminated)
Inverter has been set to accept a
generator.
Inverter will not intentionally sell to a
generator.
MATE system display only: Set ac transfer
control to grid.