Default settings and ranges, Specifications – Outback Power Systems GFX Series Inverter/Charger Operators Manual User Manual
Page 49
Specifications
900-0114-01-00 Rev A
47
Default Settings and Ranges
Table 17 12-Volt Inverter Settings
12 Vdc Inverter
Default
Minimum
Maximum
Search
Search Sensitivity
6
0
50
Search Pulse Length
8
4 20
Search Pulse Spacing
60 AC cycles
4 AC cycles
120 AC cycles
Input
AC Transfer Control
Grid
Grid or Generator
AC1/Grid Limit
50 Aac
5 Aac
60 Aac
AC2/Gen Limit
50 Aac
5 Aac
60 Aac
Inverter
Low Battery Cut-Out (LBCO)
10.5 Vdc
9 Vdc
12 Vdc
Low Battery Cut-In (LBCI)
12.5 Vdc
10 Vdc
14 Vdc
Adjust Output Voltage
120 Vac
110 vac
130 Vac
Charger
Charger Limit
11 Aac
0 Aac
12 Aac
Absorb Voltage
14.4 Vdc
13 Vdc
16 Vdc
Absorb Time Limit
1.0 hours
0.0 hours
24.0 hours
Float Voltage
13.6 Vdc
12 Vdc
15 Vdc
Float Time Period
1.0 hours
0.0 hours
24.0 hours
ReFloat Voltage
12.5 Vdc
12 Vdc
13 Vdc
Equalization Voltage
14.6 Vdc
14 Vdc
17 Vdc
Equalization Time Period
1.0 hours
0.0 hours
24.0 hours
Grid
AC1/Grid Lower Limit
108
Vac 70
Vac 110
Vac
AC1/Grid Upper Limit
132 Vac
125 Vac
140 Vac
AC1/Grid Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
Generator (Gen)
Gen Input Connect Delay
0.5 min
0.2 min
15 min
AC2/Gen Lower Limit
108
Vac 70
Vac 110
Vac
AC2/GenUpper Limit
140 Vac
125 Vac
140 Vac
AC2/Gen Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
AC2/Gen Support
ON
ON or OFF
Auxiliary (AUX)
AUX Output Control
AUTO
ON, OFF, or AUTO
AUX Output Function
Cool Fan
Cool Fan, DivertDC, DivertAC, AC Drop, Vent Fan,
Fault, GenAlert, LoadShed, or Remote
GenAlert On Voltage
11 Vdc
10 Vdc
14 Vdc
GenAlert On Delay
4 min
0 min
240 min
GenAlert Off Voltage
14 Vdc
12 Vdc
18 Vdc
GenAlert Off Delay
9 min
0 min
240 min
Load Shed Off Voltage
11 Vdc
10 Vdc
14 Vdc
Vent Fan On Set Point
13 Vdc
10 Vdc
16 Vdc
Vent Fan Off Period
5 min
0 min
30 min