Specifications – Outback Power Systems GFX Series Inverter/Charger Operators Manual User Manual
Page 52
Specifications
50
900-0114-01-00 Rev A
Table 19 48-Volt Inverter Settings
48 Vdc Inverter
Default
Minimum
Maximum
Search
Search Sensitivity
6
0
50
Search Pulse Length
8 4 20
Search Pulse Spacing
60 AC cycles
4 AC cycles
120 AC cycles
Input
AC Transfer Control
Grid
Grid or Generator
AC1/Grid Limit
50 Aac
5 Aac
60 Aac
AC2/Gen Limit
50 Aac
5 Aac
60 Aac
Inverter
Low Battery Cut-Out (LBCO)
42 Vdc
36 Vdc
48 Vdc
Low Battery Cut-In (LBCI)
50 Vdc
40 Vdc
56 Vdc
Adjust Output Voltage
120 Vac
110 vac
130 Vac
Charger
Charger Limit
11 Aac
0 Aac
12 Aac
Absorb Voltage
57.6 Vdc
52 Vdc
64 Vdc
Absorb Time Limit
1.0 hours
0.0 hours
24.0 hours
Float Voltage
54.4 Vdc
48 Vdc
60 Vdc
Float Time Period
1.0 hours
0.0 hours
24.0 hours
ReFloat Voltage
50 Vdc
48 Vdc
52 Vdc
Equalization Voltage
58.4 Vdc
56 Vdc
68 Vdc
Equalization Time Period
1.0 hours
0.0 hours
24.0 hours
Grid
AC1/Grid Lower Limit
108
Vac 70
Vac 110
Vac
AC1/Grid Upper Limit
132 Vac
125 Vac
140 Vac
AC1/Grid Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
Generator (Gen)
Gen Input Connect Delay
0.5 min
0.2 min
15 min
AC2/Gen Lower Limit
108
Vac 70
Vac 110
Vac
AC2/GenUpper Limit
140 Vac
125 Vac
140 Vac
AC2/Gen Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
AC2/Gen Support
ON
ON or OFF
Auxiliary (AUX)
AUX Output Control
AUTO
ON, OFF, or AUTO
AUX Output Function
Cool Fan
Cool Fan, DivertDC, DivertAC, AC Drop, Vent Fan,
Fault, GenAlert, LoadShed, or Remote
GenAlert On Voltage
44 Vdc
40 Vdc
56 Vdc
GenAlert On Delay
4 min
0 min
240 min
GenAlert Off Voltage
56 Vdc
48 Vdc
72 Vdc
GenAlert Off Delay
9 min
0 min
240 min
Load Shed Off Voltage
44 Vdc
40 Vdc
56 Vdc
Vent Fan On Set Point
52 Vdc
40 Vdc
64 Vdc
Vent Fan Off Period
5 min
0 min
30 min
Diversion On Voltage
58.4 Vdc
48 Vdc
64 Vdc
Diversion Off Delay
30 sec
0 sec
240 sec