Specifications – Outback Power Systems GFX Series Inverter/Charger Operators Manual User Manual
Page 50
Specifications
48
900-0114-01-00 Rev A
Table 17 12-Volt Inverter Settings
12 Vdc Inverter
Default
Minimum
Maximum
Diversion On Voltage
14.6 Vdc
12 Vdc
16 Vdc
Diversion Off Delay
30 sec
0 sec
240 sec
Stacking
Stack Phase
Master
Master, Classic Slave, OB Slave L1, 3p Classic B,
or 3p Classic C
Power Save Level
Master Adjust Only
0 0 7
Slave Adjust Only
1 1 15
Sell
Sell RE Volts
13.0 Vdc
10 Vdc
15 Vdc
Grid Tie Window
User
IEEE or User
Grid Tie Authority
GridTie
GridTie or No Sell
Calibration (Cal)
Vac Input Adjustment1
236 220 254
Vac Output Adjustment1
236 220 254
Battery Vdc Adjustment2
2 0 4
1These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower
voltages. One count equals approximately 1 Vac. The range of adjustment is 15 Vac above nominal, and 17 Vac
below nominal.
2
These values are in digital counts, not volts. One count equals 0.1 Vdc. The range of adjustment is 0.2 Vdc above or
below nominal.
Table 18 24-Volt Inverter Settings
24 Vdc Inverter
Default
Minimum
Maximum
Search
Search Sensitivity
6
0
50
Search Pulse Length
8 4 20
Search Pulse Spacing
60 AC cycles
4 AC cycles
120 AC cycles
Input
AC Transfer Control
Grid
Grid or Generator
AC1/Grid Limit
50 Aac
5 Aac
60 Aac
AC2/Gen Limit
50 Aac
5 Aac
60 Aac
Inverter
Low Battery Cut-Out (LBCO)
21 Vdc
18 Vdc
24 Vdc
Low Battery Cut-In (LBCI)
25 Vdc
20 Vdc
28 Vdc
Adjust Output Voltage
120 Vac
110 vac
130 Vac
Charger
Charger Limit
11 Aac
0 Aac
12 Aac
Absorb Voltage
28.8 Vdc
26 Vdc
32 Vdc
Absorb Time Limit
1.0 hours
0.0 hours
24.0 hours
Float Voltage
27.2 Vdc
24 Vdc
30 Vdc
Float Time Period
1.0 hours
0.0 hours
24.0 hours
ReFloat Voltage
25 Vdc
24 Vdc
26 Vdc
Equalization Voltage
29.2 Vdc
28 Vdc
34 Vdc
Equalization Time Period
1.0 hours
0.0 hours