Specifications – Outback Power Systems GFX Series Inverter/Charger Operators Manual User Manual
Page 51
Specifications
900-0114-01-00 Rev A
49
Table 18 24-Volt Inverter Settings
24 Vdc Inverter
Default
Minimum
Maximum
Grid
AC1/Grid Lower Limit
108
Vac 70
Vac 110
Vac
AC1/Grid Upper Limit
132 Vac
125 Vac
140 Vac
AC1/Grid Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
Generator (Gen)
Gen Input Connect Delay
0.5 min
0.2 min
15 min
AC2/Gen Lower Limit
108
Vac 70
Vac 110
Vac
AC2/GenUpper Limit
140 Vac
125 Vac
140 Vac
AC2/Gen Transfer Delay
6 AC cycles
0 AC cycles
240 AC cycles
AC2/Gen Support
ON
ON or OFF
Auxiliary (AUX)
AUX Output Control
AUTO
ON, OFF, or AUTO
AUX Output Function
Cool Fan
Cool Fan, DivertDC, DivertAC, AC Drop, Vent Fan,
Fault, GenAlert, LoadShed, or Remote
GenAlert On Voltage
22 Vdc
20 Vdc
28 Vdc
GenAlert On Delay
4 min
0 min
240 min
GenAlert Off Voltage
28 Vdc
24 Vdc
36 Vdc
GenAlert Off Delay
9 min
0 min
240 min
Load Shed Off Voltage
22 Vdc
20 Vdc
28 Vdc
Vent Fan On Set Point
26 Vdc
20 Vdc
32 Vdc
Vent Fan Off Period
5 min
0 min
30 min
Diversion On Voltage
29.2 Vdc
24 Vdc
32 Vdc
Diversion Off Delay
30 sec
0 sec
240 sec
Stacking
Stack Phase
Master
Master, Classic Slave, OB Slave L1, 3p Classic B,
or 3p Classic C
Power Save Level
Master Adjust Only
0 0 7
Slave Adjust Only
1 1 15
Sell
Sell RE Volts
26 Vdc
20
30
Grid Tie Window
IEEE
IEEE or User
Grid Tie Authority
GridTie
GridTie or No Sell
Calibration (Cal)
Vac Input Adjustment1
236 220 254
Vac Output Adjustment1
236 220 254
Battery Vdc Adjustment2
2 0 4
1These values are in digital counts, not volts. Lower counts stand for higher voltages, and higher counts mean lower
voltages. One count equals approximately 1 Vac. The range of adjustment is 15 Vac above nominal, and 17 Vac
below nominal.
2
These values are in digital counts, not volts. One count equals 0.2 Vdc. The range of adjustment is 0.4 Vdc above or
below nominal.