Error messages, 36). it, Troubleshooting – Outback Power Systems GFX Series Inverter/Charger Operators Manual User Manual
Page 38

Troubleshooting
36
900-0114-01-00 Rev A
Error Messages
An Error message is caused by a critical fault. In most cases when this occurs, the unit will shut down 
and the inverter’s ERROR LED (see page 11) will illuminate. See the system display manual for 
instructions on viewing errors. One or more messages will display yes. If a message says no, it is not 
the cause of the error. 
Error screens can only display errors; they cannot clear them. It is possible to clear an error by 
resetting the inverter. The inverter must be turned off, and then on, to reset it. Other possible 
remedies are shown below (although it is still necessary to reset the inverter). 
Table 5 Error Troubleshooting
Message Causes
Possible
Remedy
low ac output 
voltage 
Inverter’s AC regulation cannot be 
maintained under high load conditions. 
Check loads and measure current draw. Remove loads as 
necessary. 
stacking error 
detected 
Programming problem among stacked 
units. (Often occurs if there is no 
master.) Can also occur when ac output 
backfeed occurs. 
Check stacking programming and designation of master. (See 
page 24.) 
Check for output backfeed from an external source. Disconnect 
output if necessary. 
inverter 
overtemp 
Inverter has exceeded its maximum 
allowed operating temperature. 
Allow the inverter to remain off for a short time to reduce the 
temperature, or add external cooling. 
This error can occur without shutting off the inverter, if the 
inverter is in Sell mode. (This error turns off the inverter’s 
output, but not the input.) It may be necessary to manually 
shut the inverter off. If an extra inverter is added to the system, 
this will distribute the sell current more widely and allow each 
unit to run cooler. 
low battery 
voltage 
DC voltage is below Low Battery Cut-Out 
(LBCO) set point. 
This error can be triggered by other 
causes. It can appear along with low AC 
output voltage, AC output shorted, or 
ac output backfeed errors. 
If this error accompanies other errors, treat those conditions as 
appropriate. 
If it occurs by itself: Recharge the batteries. The error will clear 
automatically if an external AC source is connected and the 
inverter’s charger comes on. 
phase loss 
error 
A slave was ordered to transfer to AC by 
the master, but no AC is present. The 
unit continues inverting. This is the only 
“Error” that is not accompanied by a 
shutdown. 
Check the AC voltage on the inverter input terminals. If AC 
voltage is not present, problem is external. If AC voltage is 
present, the unit may be damaged. Contact OutBack Technical 
Support (see inside front cover of this manual). 
high battery 
voltage 
DC voltage exceeded acceptable level 
(specified on page 13). 
Check the charging source. This problem is usually the result of 
external charging. This error will clear automatically if 
conditions are removed. 
ac output 
shorted 
Inverter exceeded its maximum surge 
current due to severe overload. 
Check the loads and wiring. This problem is more often the 
result of a wiring error (a short). 
ac output 
backfeed 
Usually indicates another AC power 
source (out of phase with the inverter) 
was connected to the unit’s AC output. 
Disconnect the AC OUT wires from the inverter. Check the 
wires (not the inverter) with an AC voltmeter. If an AC source is 
present, shut it off. 
