Hot-plug power supply calculations – HP ProLiant DL360p Gen8 Server User Manual
Page 102

Specifications 102
DC source and the point of connection of the earthing electrode conductor.
CAUTION:
To reduce the risk of electric shock or energy hazards:
•
This equipment must be installed by trained service personnel, as defined by the NEC and IEC
60950-1, Second Edition, the standard for Safety of Information Technology Equipment.
•
Connect the equipment to a reliably grounded SELV source. An SELV source is a secondary
circuit that is designed so normal and single fault conditions do not cause the voltages to
exceed a safe level (60 V DC).
•
The branch circuit overcurrent protection must be rated 24 A.
HP 1200W Common Slot Platinum Plus Hot Plug Power Supply
(94% efficiency)
Specification
Value
Input requirements
Rated input voltage
100 to 120 VAC, 200 to
240 VAC
Rated input frequency
50 Hz to 60 Hz
Rated input current
9.1 A at 100 VAC
6.7 A at 200 VAC
Maximum rated input power
897 W at 100V AC input
1321 W at 200V AC input
Btus per hour
3408 at 120V AC input
4433 at 200V to 240V AC input
Power supply output
Rated steady-state power
800 W at 100V AC input
900 W at 120V AC input
1200 W at 200V to 240V AC
input
Maximum peak power
800 W at 100V AC input
900 W at 120V AC input
1200 W at 200V to 240V AC
input
Hot-plug power supply calculations
For hot-plug power supply specifications and calculators to determine electrical and heat loading for the
server, see the HP Power Advisor website