Hot-plug power supply calculations – HP ProLiant DL360p Gen8 Server User Manual

Page 102

background image

Specifications 102

DC source and the point of connection of the earthing electrode conductor.

CAUTION:

To reduce the risk of electric shock or energy hazards:

This equipment must be installed by trained service personnel, as defined by the NEC and IEC

60950-1, Second Edition, the standard for Safety of Information Technology Equipment.

Connect the equipment to a reliably grounded SELV source. An SELV source is a secondary

circuit that is designed so normal and single fault conditions do not cause the voltages to
exceed a safe level (60 V DC).

The branch circuit overcurrent protection must be rated 24 A.

HP 1200W Common Slot Platinum Plus Hot Plug Power Supply

(94% efficiency)

Specification

Value

Input requirements

Rated input voltage

100 to 120 VAC, 200 to
240 VAC

Rated input frequency

50 Hz to 60 Hz

Rated input current

9.1 A at 100 VAC

6.7 A at 200 VAC

Maximum rated input power

897 W at 100V AC input
1321 W at 200V AC input

Btus per hour

3408 at 120V AC input

4433 at 200V to 240V AC input

Power supply output

Rated steady-state power

800 W at 100V AC input

900 W at 120V AC input
1200 W at 200V to 240V AC

input

Maximum peak power

800 W at 100V AC input

900 W at 120V AC input
1200 W at 200V to 240V AC

input

Hot-plug power supply calculations

For hot-plug power supply specifications and calculators to determine electrical and heat loading for the

server, see the HP Power Advisor website (

http://www.hp.com/go/hppoweradvisor

).