Rack pdu configuration – American Power Conversion AP7610 User Manual
Page 8
8
Rack Power Distribution Unit — AP7610
Rack PDU Configuration
How to configure
through a serial port
connection
1. Connect an available serial port on your computer to the serial port
on the Rack PDU (shown below), using the supplied configuration
cable (940-0144).
2. Run a terminal emulation program such as Windows
®
HyperTerminal.
3. Configure the following settings for the serial port:
– 19,200 bps
– no parity
– 8 data bits
– 1 stop bit
– no flow control
4. Press any key on the computer to display the Rack PDU login
screen, which contains the username and password prompts.
5. Log on by using the user name and password for the appropriate
access level:
l
Note
Some terminal emulation programs require that a
device be disconnected and then reconnected for
the new serial port settings to take effect.
Access Level
Default
User Name
Default Password
Administrator
Press
E
NTER
.
Type apc (in
lowercase).
User
Press
E
NTER
.
Press
E
SC
.
- 5000VA (25 pages)
- MX28B-400 (46 pages)
- CTEG4-240MB-5 (7 pages)
- 200/208 V (52 pages)
- VS 100 (54 pages)
- SMARTUPS 700 (60 pages)
- AP7562J (24 pages)
- 100VAC (18 pages)
- Smart-UPS VT (56 pages)
- 1400XLT (30 pages)
- 350/550 (2 pages)
- SURTA1500XLJ (16 pages)
- RT-UXI (20 pages)
- 208 Vac (17 pages)
- 2200 VA (17 pages)
- 1500VA (18 pages)
- Smart-UPS (36 pages)
- 60-80kW 208/480V (34 pages)
- 420 (3 pages)
- 220 VAC (21 pages)
- 350 (2 pages)
- AP9215 (20 pages)
- Back-UPS CS 500 (2 pages)
- PDU (54 pages)
- Airless Paint Sprayer 68001 (24 pages)
- AP7902 AP7911 (26 pages)
- UPS (2 pages)
- RT XLI/XLICH (34 pages)
- 990-2233A (19 pages)
- 208/220 (48 pages)
- NS 600 (2 pages)
- SYMF800KH (54 pages)
- 20-30 kVA 480V (4 pages)
- 100 VAC (25 pages)
- 750 (17 pages)
- 3000 (23 pages)
- MX28B200 (61 pages)
- RS 1000 (2 pages)
- 200-240 VAC (21 pages)
- 5000RMB (23 pages)
- 480kW400V (32 pages)
- AP9825I (1 page)
- 250/450 (2 pages)
- SUA48RMXLBP3U (8 pages)