beautypg.com

13 voltage designation label, 5 testing, 1 quality control – ADC 70 User Manual

Page 29: 2 resistance test, 3 wiring connections torque measurements, 4 power indication test, Testing, Quality control, Resistance test, Wiring connections torque measurements

background image

ADCP-80-524 • Issue 1 • November 2001

Page 29

©

2001, ADC Telecommunications, Inc.

4.13 Voltage Designation Label

Write

the voltage used in the fuse panel on the voltage designation label (see

Figure 9

)

and

attach

the label to the back of the panel.

5

TESTING

5.1

Quality Control

Each

unit is thoroughly tested at the ADC factory. The following tests are recommended,

however,

to assure that no damage has occurred during shipping or handling. Both bus A and

bus

B circuits need to be tested. The tests in

Subsection 5.2,

Resistance Test

and

Subsection 5.3,

Wiring

Connections Torque Measurements

must be performed without power applied to the

fuse

panel.

5.2

Resistance Test

Measure

the resistance at each bus input connector using a multi meter connected to the BATT

and

RTN input terminals. A resistance of at least 500 ohms should be read on the meter (some

meters

will indicate a resistance of several Megohms because their input voltage is not high

enough

to break down the forward conductance of the diodes used in the alarm circuit). Any

resistance

higher than 500 ohms is acceptable.

5.3

Wiring Connections Torque Measurements

Measure

the torque of all input, output, and fuse failure alarm relay contact connections

included

in the non-powered testing paragraphs above using a torque screwdriver that is

calibrated

in pound-force inches or Newton meters. The torque specifications are printed on the

rear

of the fuse panel adjacent to each connector.

5.4

Power Indication Test

After

checking input resistance and verifying the wiring connections torque, power may be

applied

to the fuse panel. Upon power application, the alarm indicators should not light unless

there

is a fuse that has failed. The alarm relay contacts should provide an open circuit between the

common

(C) terminals and the normally open (NO) terminals and a closed circuit between the

common

(C) and normally closed (NC) terminals.

Caution:

This equipment employs electrical voltage and amperage levels which may be

considered

an electrical hazard. Care should be exercised to assure that only qualified personnel

are

allowed to install, operate, maintain, or otherwise come in contact with the fuse panel when

it

is energized. Only insulated tools should be used on energized elements of the panel.

Caution:

Before performing this test, verify that the input and output power is not applied to the

fuse

panel connectors,