mounting

brackets allow mounting with WECO 1.00-inch (2.54 cm) hole spacing or EIA 1.25-

inch

(3.18 cm) hole spacing. The slotted mounting hole pattern in the mounting brackets

compensates

for vertical rack differences and allows mounting the fuse panel in either 1.75- or

2-inch

(4.45 or 5.08 cm) rack spaces.

1.23 Environmental Characteristics

The

environmental characteristics of the PowerWorx Type 70 Series Power Distribution Fuse

Panel

are listed in

Table 1

.

2

ACCESSORIES

The

following accessories for the PowerWorx Type 70 fuse panel are available:

• Standard

Type 70 fuses with current capacity of from 0.2 Amp to 10.0 Amps

• Cable

management bar with mounting screws. Provides cable tie points. Installed at rear

of

fuse panel by fastening ends of bar to both sides of the panel

• Four

sizes of two-hole compression lugs for #2, #4, #6, and #14 AWG wire for input

power

connection

• Kit

of perforated fuse value designation cards and plastic covers

• Kit

of fused equipment designation cards, a card holder, and a plastic cover

Table 1. PowerWorx Type 70 Fuse Panel Environmental Characteristics

PARAMETER

DESCRIPTION

Operating

temperature

–5°

C to +50° C

Storage

temperature

–45°

C to +85° C

Humidity

range

0%

to 95% humidity (non-condensing)

Altitude

range

–197

ft. (0.06 km) to 13,000 ft. (3.96 km) above sea level

Fire

rating

All

components UL94-V1 or better

Acoustic

noise

0

dBA above ambient

Heat

dissipation (fully loaded

traditional

panel)

40

watts maximum@ 65 A per bus, 80 watts maximum @ 130 A

total

fuse panel load

Heat

dissipation (no load)

1

watt per bus