23 environmental characteristics, 2 accessories, Accessories – ADC 70 User Manual
Page 17
ADCP-80-524 • Issue 1 • November 2001
Page 17
©
2001, ADC Telecommunications, Inc.
mounting
brackets allow mounting with WECO 1.00-inch (2.54 cm) hole spacing or EIA 1.25-
inch
(3.18 cm) hole spacing. The slotted mounting hole pattern in the mounting brackets
compensates
for vertical rack differences and allows mounting the fuse panel in either 1.75- or
2-inch
(4.45 or 5.08 cm) rack spaces.
1.23 Environmental Characteristics
The
environmental characteristics of the PowerWorx Type 70 Series Power Distribution Fuse
Panel
are listed in
.
2
ACCESSORIES
The
following accessories for the PowerWorx Type 70 fuse panel are available:
• Standard
Type 70 fuses with current capacity of from 0.2 Amp to 10.0 Amps
• Cable
management bar with mounting screws. Provides cable tie points. Installed at rear
of
fuse panel by fastening ends of bar to both sides of the panel
• Four
sizes of two-hole compression lugs for #2, #4, #6, and #14 AWG wire for input
power
connection
• Kit
of perforated fuse value designation cards and plastic covers
• Kit
of fused equipment designation cards, a card holder, and a plastic cover
Table 1. PowerWorx Type 70 Fuse Panel Environmental Characteristics
PARAMETER
DESCRIPTION
Operating
temperature
–5°
C to +50° C
Storage
temperature
–45°
C to +85° C
Humidity
range
0%
to 95% humidity (non-condensing)
Altitude
range
–197
ft. (0.06 km) to 13,000 ft. (3.96 km) above sea level
Fire
rating
All
components UL94-V1 or better
Acoustic
noise
0
dBA above ambient
Heat
dissipation (fully loaded
traditional
panel)
40
watts maximum@ 65 A per bus, 80 watts maximum @ 130 A
total
fuse panel load
Heat
dissipation (no load)
1
watt per bus