TOHO ELECTRONICS TRM-006A User Manual
Page 37

37
MODBUS address
Identifier
Low-level
W
High-level
W
Character
Name
R/W
Description
□DP
30
31
^
Q F
Set a decimal position
R/W
R/W the decimal position setting
No decimal point: 00000
Tenth: 00001
For analog input, following available:
Hundredth: 00002
Thousandth: 00003
LOC
34
35
^ o Q F
Set a key lock
R/W
R/W the key lock setting
SLH
36
37
^ o Q F
Set a scaling upper limit
R/W
R/W the PV range upper limit setting
SLL
38
39
^ o Q F
Set a scaling lower limit
R/W
R/W the PV range lower limit setting
E1F
94
95
^ o Q F
Set a PV event output 1
function
R/W
R/W the PV event output 1 function
setting
E1H
96
97
^ o Q F
Set an event output 1 upper
limit
R/W
R/W the event output 1 upper limit setting
E1L
98
99
^ o Q F
Set an event output 1 lower
limit
R/W
R/W the event output 1 lower limit setting
E1C
100
101
^ o Q F
Set an event output 1
sensitivity
R/W
R/W the event output 1 sensitivity setting
E1T
102
103
^ o Q F
Set an event output 1 delay
timer
R/W
R/W the event output 1 delay timer setting
E1B
104
105
^ o Q F
Set a special event output 1
function
R/W
R/W the special event output 1 function
setting
E1P
106
107
^ o Q F
Set an event output 1
polarity
R/W
R/W the event output 1 polarity setting
E2F
112
113
^ o Q F
Set a PV event output 2
function
R/W
R/W the PV event output 2 function
setting
E2H
114
115
^ o Q F
Set an event output 2 upper
limit
R/W
R/W the event output 2 upper limit setting
E2L
116
117
^ o Q F
Set an event output 2 lower
limit
R/W
R/W the event output 2 lower limit setting
E2C
118
119
^ o Q F
Set an event output 2
sensitivity
R/W
R/W the event output 2 sensitivity setting
E2T
120
121
^ o Q F
Set an event output 2 delay
timer
R/W
R/W the event output 2 delay timer setting
E2B
122
123
^ o Q F
Set a special event output 2
function
R/W
R/W the special event output 2 function
setting
E2P
124
125
^ o Q F
Set an event output 2
polarity
R/W
R/W the event output 2 polarity setting
PRT
136
137
^ o Q F
Set a communications
protocol
R/W
R/W the communications protocol setting
Special-purpose protocol: 00000
MODBUS (RTU): 00001
MODBUS (ASCII): 00002
COM
138
139
^ o Q F
Set a communications
parameter
R/W
R/W the communications parameter
setting
Example: □B8N2
BPS
140
141
^ o Q F
Set a communications
speed
R/W
R/W the communications speed setting
Example: 00096 (if 9600 bps)
ADR
142
143
^ o Q F
Set a communications
address
R/W
R/W the communications address setting
AWT
144
145
^ o Q F
Set a response delay
R/W
R/W the response delay setting
MOD
146
147
^ o Q F
Set communications mode
switchover
R/W
R/W the communications mode
switchover setting
RO: 00000
RW: 00001
TRF
160
161
^ o Q F
Set a transmission output
function
R/W
R/W the transmission output function
setting
TRP
162
163
^ o Q F
Set a forward/reverse
operation switchover for
transmission output
R/W
R/W the forward/reverse operation
switchover setting for transmission output