6.8 Composition of an ASCII request message (transmitted from a high-level
computer to this product)
n For the codes a) through g), see "6.10 Description of ASCII codes."
6.8.1 Composition of a read request message
a) Start code
“:”
b) Slave address
“1” , “B”
c) Function code
“0” , “3”
High level
“0” , “0”
d) Register address
Low level
“0” , “0”
First register address
High level
“0” , “0”
e) Number of registers
Low level
“0” , “2”
Fixed at 2
f)
LRC
“E” , “0”
g) End code
CR, LF
6.8.2 Composition of a write request message
a) Start code
“:”
b) Slave address
“0” , “3”
c) Function code
“1” , “0”
High level
“0” , “0”
d) Register address
Low level
“C” , “0”
First register address
High level
“0” , “0”
e) Number of registers
Low level
“0” , “2”
Fixed at 2
h) Number of data items
“0” , “4”
Number of registers
×
2
High level
“0” , “0”
③
Data for the first register
(a low-level word)
Low level
“6” , “F”
④
High level
“0” , “0”
①
i)
Data for the first register + 1
(a high-level word)
Low level
“0” , “0”
②
When writing ①, ②, ③, and
④ H in the data, write them in
the order described on the
left-hand side. (① represents 1
byte.)
f)
LRC
“E” , “0”
g) End code
CR, LF