TOHO ELECTRONICS TTM-10L User Manual
Page 6

DEFINITIONS AND FUNCTIONS
7
7
7
7.
.
.
.
ADDITIONAL FUNCTIONS
7.1
Stand-by Sequence
This is the function not to turn on Alarm Output even if it covers the conditions to activate Alarm
・
・・・
Output at Power ON. This function is valid when the Power turns on at the part of
slanting line
a
of the following Alarm Output Function Chart.
Alarm Output Hold
This function holds the condition of Alarm Output after the Alarm Output has started to activate.
・
・・・
For release of this function,
Power turn on again or setting the position of UNHOLD
make
at Additional Function Setting.
7.2
PV
ALARM OUTPUT
Alarm Output makes Alarm Output Relay ON/OFF as PV corresponds to Alarm Output PV.
Alarm Output Function Chart
・
Deviation High and Low Limit
Absolute Value High and Low Limit
△
SV
0℃()
Deviation High Limit
Absolute Value High Limit
△
SV
0℃()
Deviation Low Limit
Absolute Value Low Limit
△
SV
0℃()
Deviation High and Low Limit range
Absolute Value High and Low Limit range
△
SV
0℃()
Range of Alarm Output
Alarm Output Setting Low Limit
Alarm Output Setting
Limit
:
:
:
High
ensitivity
:Alarm Output s
7.3
INPUT DISPLAY RANGE AND SETTING RANGE
( JIS C 1602−1995)
CHART 1 DISPLAY RANGE & SETTING RANGE OF THERMOCOUPLE INPUT
Setting Range
Display Range
Setting Range
Display Range
K
゚
゚C
0∼1200
−40∼1326
N
゚C
0∼1300
0∼1335
゚F
0∼2200
−40∼2420
゚F
32∼2350
32∼2435
J
゚C
0∼800
−31∼850
W5Re/
゚C
0∼2300
0∼2336
゚F
0∼1450
−24∼1563
W26Re
゚F
32∼4200
32∼4236
E
゚C
0∼800
−24∼833
R
゚C
0∼1700
0∼1755
゚F
0∼1450
−16∼1531
゚F
32∼3100
32∼3192
T
゚C
−200∼400
−231∼407
S
゚C
0∼1700
0∼1730
゚F
−330∼750
−385∼765
゚F
32∼3100
32∼3146
(JIS C 1604−1997)
CHART 2 DISPLAY RANGE & SETTING RANGE OF R.T.D. INPUT
Setting Range
Display Range
Setting Range
Display Range
(
)
(
)
With Decimal
With Decimal
Pt100
゚C
−199∼500
−199∼539
−199.9∼500.0
−199.9∼539.1
゚F
−199∼950
−199∼999
−199.9∼950.0
−199.9∼999.9
JPt100
゚C
−199∼500
−199∼529
−199.9∼500.0
−199.9∼529.1
゚F
−199∼950
−199∼984
−199.9∼950.0
−199.9∼984.4
CHART 3 DISPLAY RANGE & SETTING RANGE OF CURRENT
Setting Range
Display Range
4∼20mADC
−1999∼9999/
Displays approx.±12% wider
−199.9∼999.9/
then setting range.
−19.99∼99.99