Chapter 6: Troubleshooting
60 of 93
CC = Compressor Critical
SC = System Critical
PC = Process Critical
W = Warning
Alarm Name
#
Type
Possible Cause
Solution
Pump 2 Overload
53
SC/W
Motor circuit protector open
Verify motor circuit protector
operation. Verify motor wiring
and amp draw while under load.
Pump flow rate in excess of
capacity
Verify system valves are
operational and properly set.
Contact customer service or
sales if pump is sized too small
for application.
High Temp Safety Switch
54
PC
Heater failure
Verify operation of heater and
cooling valve. .
Cooling Valve failure
Verify wiring at cooling valve
and at terminal bloc
Sensor failure
Replace sensor if necessary.
Phase Monitor Fault
55
SC
Unit wired incorrectly
Reverse two wires at line-side
of power switch on electrical
panel.
Loss of phase during
operation
Verify sensor wiring at sensor
and at terminal bloc.
Sensor failure
Replace sensor if necessary.
From Proc Sensor Failure
56
W
Sensor wires loose from
controller terminal block
Verify wiring at sensor and at
terminal block. y.
Sensor wires broke between
sensor and controller terminal
block.
Replace sensor if necessar
Non-Controller Related Issues
Problem
Possible cause
Solution
Unit does not run.
No power.
Check main disconnect, fuses, wiring,
and power lead to unit.
Wrong voltage supplied to unit.
Voltage must be within plus or minus
10% of nameplate rating.
Control circuit fuse blown.
Replace control circuit fuse.
Check transformer.
Check for a short circuit.
Defective control transformer.
Replace.
Piping flow switch circuit open.
Add water or water/glycol solution as
required.
Pump motor off on overload.
Reset and test.