Terminal block diagram (analog outputs and digital option)
Type D and W (horizontal mount)
Notes:
Terminal K1-3: this terminal (protective or earth ground) is not tied with GND. If so desired, K1-3 can be tied
with GND by closing a solder pad on the PCB (B18)
USB or TCP/IP port: this port is optional
Measuring humidity or temperature only
Operation of the HF54 does not require both current loops to be closed. When using the HF54 to measure
either humidity only or temperature only, close only the loop that is being used.
Using the ROTRONIC HW4 software, any unused output of the HF54 can be disabled.
Terminals
Description
K1-1: GND
Power supply (-) or neutral
K1-2: V+
Power supply: 15…40 VDC (+)
or 12…28 VAC (Phase)
K1-3: -
►
Protective ground (see note below)
Terminals
Description
K2-4: GND
Ground (tied with other GND)
K2-3: GND
Ground (tied with other GND)
K2-2: OUT2
Temperature output (+)
K2-1: OUT1
Relative humidity or dew point (+)
Terminals
Description
K3-4: D-
RS-485 Bi-directional
TX- / RX -
K3-3: D+
RS-485 Bi-directional
TX+ / RX +
K3-2: GND
Ground
K3-1: PWR
Not used