2.2 Insulation Test

Measure Therma Cable’s insulation resistance at each step using a
megohmeter (Fig. 2.2) and record readings on the measures’ table (this
label is available at the opening of the product).

IMPORTANT!

For the warranty to be valid, fill out the measures’ table and ensure that the
10 readings have been correctly noted.

A qualified electrician must measure the system’s insulation resistance as follows:

– Use a calibrated megohmeter only;

– Measure insulation resistance at the free end of the cold lead, between the

phase conductor and ground;

cold lead

Fig. 2.2

CAUTION! Dangerous Test

– Write the reading in the measures’ table;

– This reading must be over 1,000,000 ohms;

– If the reading is under 1,000,000 ohms, stop work and contact

Ouellet Canada Inc.’s technical specialists at 1 800 463-7043.