Ouellet OAV User Manual
Installation instructions “oav” series
180, 3rd Avenue / P.O. Box 188, L’ISLET, Qc, G0R 2C0
Tel.: (418) 247-3947, 1-800-463-7043
Fax: (418) 247-7801
www.ouellet.com
INSTALLATION INSTRUCTIONS
“OAV” Series
LOCATION OF THE HEATER
AND WALL THERMOSTAT
1- Use only the four brackets to hang heater.
2- Connect thermostat to T1, T2 connectors. (See wiring
diagram inside of the control box cover).
3- Connect sources to L1, L2 and if necessary L3 connectors.
(See wiring diagram).
4- The fan only switch must be connect on T1, T3 terminal.
(See wiring diagram).
5- Air inlet and outlet must be free from interferences such as
columns, machinery and partition wall.
6- Locate thermostat on interior partition wall or post
(insulate from cold steel post). Install thermostat away
from cold drafts, internal heat sources and from heater
discharge.
POWER SUPPLY CONNECTIONS
The power supply may be single or three phases as shown
on the nameplate. Wiring diagrams are inside of the control
box cover. Wire heater in accordance with local and national
codes.
TEST
- To test unit heater temporarily set thermostat at maximum
temperature.
- Make sure that the fan rotates in the correct direction;
airflow should be in the direction of the arrow such as
indicated on the drawing.
LUBRICATION OF MOTOR
The motor includes sealed lubrication-free bearings.
OVERHEATING PROTECTION
The motor and the heating elements are protected against
overheating by automatic thermal high-limits.
Cycling of either ligh-limits is an indication of abnormal
operation and should be corrected at once.
FAN DELAY
This unit is equiped with a timed fan delay which keeps the
fan stopped at the beginning to let the heating element warm-
up. The same fan delay keep the fan going when the heater is
stopped to dispell residual heat.
MAINTENANCE
Once a year, remove the dust accumulation inside the
heater using a vacuum cleaner or compressed air. Clean-
ing should be done while the heater is disconnected from
the supply circuit.
A qualified technician should perform any other
servicing.
WARRANTY
OUELLET CANADA INC. warrants the component
parts of its products against defects in material and
workmanship for a one year period following the date
of purchase, under normal use and service, when proof
of purchase of such is provided to the manufacturer. The
obligation of Ouellet Canada inc., under the terms of this
warranty, will be to supply a new unit and this releases
the manufacturer from paying the installation costs or
other secondary charges linked to replacing the unit or
the component part(s).
ATTENTION
Basic precautions should always be followed to reduce
the risk of fire, electric shock, and injury to persons.
-Read all instructions before using this heater.
-This heater is hot when in use. To avoid burns, do not let
bare skin touch hot surfaces. Keep combustible materials
at least 24 in. (610 mm) from the front of the heater.
-Minimum clearance from the walls and ceiling:
24 in. (610 mm).
-Install at least 8 ft (2.5 m) from the floor.
-Do not use outdoors.
-Do not insert or allow foreign objects to enter any ven-
tilation or exhaust opening as this may cause an electric
shock or fire, or damage the heater.
-Do not block air intakes or exhaust in any manner.
-A heater has hot and arcing or sparking parts inside. Do
not use it in areas where gasoline, paint, or flammable
liquids are used or stored.
-Use this heater only as described in this manual. Any
other use not recommended by the manufacturer may
cause fire, electric shock, or injury to persons.
RECOMMENDED MAXIMUM MOUNTING HEIGHTS
5 - 10KW
15 - 30KW
40 - 60 KW
m ft m ft m ft
WITHOUT H
3.7
12
5.5
18
8.3
27
CONE S
5.8 19 8.5 20 13 42
SINGLE H
2.5
8
3.7
12
4.3
14
CONE S
6.9 22 10 33 11.8
38
TRIPLE H
3.1
10
4.3
14
6.1
20
CONE S 9.5 31 13.2 43 15.5 50
JET
H
4.9
16
6.7
22
9.1
30
CONE S 6.1 20 8.5 26 11.9 40
H
S
H
S
H
S
H
S
KEEP THIS INSTRUCTION PAMPHLET
FOR THE USER INS21-200207-02
610
24
B
610
24
A
C
SUPPORT BRACKETS
DIMENSIONS
mm
inches