NORD Drivesystems TI 275281172 User Manual
Page 5
PROFINET IO Bus module – SK TU4-PNT-M12-C
TI 275281172 - 4913
5 / 8
Pos : 24 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ PROF INET IO /LED Anzeigen- PROF INET spezifisc he LED [PN T Allgemein] @ 4\ mod_1385130089638_388.doc x @ 106275 @ @ 1
PROFINET-specific LED
RUN
(Ethernet State)
Meaning
BF
(Ethernet Error)
Meaning
OFF
No operating voltage
Initialisation
OFF
No error
Flashing green
No connection to PROFINET IO controller
No parameter communication
No process data communication
Flashing red
No process data communication
à e.g. wrong GSDML file
Green ON
Parameter communication active
Process data communication active
Red ON
Ethernet error
à there is no physical
connection to a further participant
Double-flashing
red
(2 x 0.25 s,+
1sec pause)
PROFINET or FI timeout,
(see also P151, P513)
Link
(Green LED)
Activity
(Yellow LED)
Meaning
OFF
OFF
•
Module not ready, no control voltage.
•
No bus connection (check cable connection)
ON
OFF
•
Bus connection (cable connection) to another Ethernet device exists
•
No bus activity
ON
Flashing
(Blinking)
•
Bus connection (cable connection) to another Ethernet device exists
•
Bus activity present
Pos : 25 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/ LED Anz eigen- N ORD s pezifisc he LED [EI P / PO L / ECT / PNT Allgemei n] @ 3\ mod_1363773424248_388. doc x @ 61815 @ @ 1
NORD-specific LEDs
DS
(Device status)
DE
(Device error)
Meaning
Long flash
= 0.5 s on / 1 s off
Short flash
= 0.25 s on / 1 s off
OFF
OFF
Module not ready, no control voltage.
ON
OFF
Module ready, no error, at least one frequency inverter is communicating via the system bus
ON
Short flashing
Module ready, but
•
One or more of the connected frequency inverters has fault status
Long flashing
OFF
Module ready and at least one other participant is connected to the system bus, but
•
no frequency inverter connected to system bus (connection may be interrupted)
•
one or more system bus clients has address error
•
Software incompatible (module software and FI software do not match - update required)
Long flashing
Short flashing
Flash interval
1 x - 1s pause
System bus is in status "Bus Warning"
•
Communication on system bus disrupted
•
No other clients available on system bus
•
Module not inserted correctly or no connection to the system bus
•
Frequency inverter has no supply voltage
Long flashing
Short flashing
Flash interval
2 x - 1s pause
System bus is in status "Bus Off"
•
the system bus 24V power supply was interrupted during operation
Long flashing
Short flashing
Flash interval
3 x - 1s pause
System bus is in status "Bus Off"
•
No system bus 24V power supply
Long flashing
Short flashing
Flash interval
4 x - 1s pause
Module error
•
see parameter P170
OFF
Short flashing
Flash interval
1…7 - 1s pause
System error, internal program sequence interrupted
•
EMC interference (observe wiring guidelines!)
•
Module defective
Pos : 26 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ PROF INET IO /Fehl ermeldungen Pr ofi net Baugruppen allgemein [SK xU x-PNT - Allgemein] @ 4\mod_1384961728468_388. doc x @ 105889 @ 5 @ 1