Module features, Installation – NORD Drivesystems TI 275281172 User Manual
Page 2
PROFINET IO Bus module – SK TU4-PNT-M12-C
2 / 8
TI 275281172 - 4913
Digital input - working area
Low: 0 V … 5 V, High: 15 V … 30 V
Digital input - specific data
R
i
= 8 kΩ, input capacity: 10 nF, response time 3 ms,
inputs as per EN 61131-2 type 1
Digital output - 24 VDC power supply
≤ 400 mA (input)
Digital output - working range
Low = 0 V, High = 24 V; max. 200 mA
Bus specification
EtherNet/IP
Max. 100 MBaud
Cable
Min. Ethernet CAT-5
Electrical isolation 500 V
eff
Max. cable length
100 m between two
modules
Bus connection
2 x M12 sockets
Shield
via M12 direct to PE
Bus termination
performed automatically
PE connection
via PE screw connection
Status display
8 LEDs
in the terminal box
Topology
Star, tree, ring, linear bus
Performance
Update interval for process data between module and frequency inverter
≤ 5 ms
Parameter read access on the frequency inverter
≈ 15 ms
Parameter write access with storage in EEPROM
≈ 25 ms
Cycle times
≥ 1 ms
Pos : 8 /T ec hnis che Inf or mationen/ SK xU x - Bus - Er wei ter ung en/ PR OFIN ET I O/M er kmal e [ PNT Allgemei n] @ 4\ mod_1385365458675_388. doc x @ 106301 @ 5 @ 1
Module features
Communication
RT (Real Time)
à Real time communication of process data
IRT (Isochronous Real Time)
à Isochronous real time communication of synchronised
process data
Addressing
Automatic address assignment via IO controller using DCP
(Discovery Configuration Protocol)
Data transfer
via Switched Ethernet
Autonegotiation
Negotiation of transfer parameters
Autocrossover
Transmission and receiver cables are automatically
crossed in the switch as necessary
Conformity classes
CC-B, and CC-C
Access for NORD diagnosis tool via
diagnosis socket on the device (if available) and possibly
via frequency inverter and
Ethernet protocols UDP or TCP/IP
Pos : 11 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/M ontage [ SK TU4- xxx- xxx] @ 2\ mod_1353315135994_388. doc x @ 51251 @ 5 @ 1
Installation
The module must be attached to the suitable connection unit (SK TI4-TU- …) and connected using the
four M4 x 40 mm provided hexagon socket collar screws. Installation details can be found in the data
sheet for the relevant connection units.
Pos : 14 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/ Ans chl üss e - Et her netsei te - Variant e M12 [SK TU 4-.. .EIP/ ECT/ PO L/ Ansc hlüss e - Et hernets eit e - Variant e M 12 [ SK TU4-. .. EIP/ECT /POL/PNT(-M 12). ..-C)] @ 4\ mod_1385383150995_388.doc x @ 106697 @ 5 @ 1