Led displays – NORD Drivesystems TI 275271019 User Manual
Page 5

EtherNet/IP Bus module – SK CU4-EIP
TI 275900150 - 4913
5
LED displays
The operating statuses of the module are visualised using LED indicators.
No.
Name
Colour
Meaning
1
MS
dual (red/green)
Module status
NS
dual (red/green)
Network status
2
DS
green
Device status
DE
red
Device error
3
L/A 1
Dual (green/yellow)
Link/Activity 1
L/A 2
Dual (green/yellow)
Link/Activity 2
Pos : 20 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Et herN et/ IP/LED Anz eigen- EtherNet/I P s pezifisc he LED [EIP Allgemein] @ 3\ mod_1363774926130_388. doc x @ 61840 @ @ 1
EtherNet/IP-specific LEDs
MS
(Module status)
Meaning
NS
(Network status)
Meaning
OFF
No operating voltage
OFF
No operating voltage
Flashing green
Module not configured
Flashing green
IP address configured but no CIP connection
available
green
Module working correctly
green
CIP connection(s) available
Flashing red
Minor error, faulty configuration
Flashing red
Time-out, an "exclusive owner connection"
has a time-out error
red
Unrecoverable error
red
Dual IP whose IP address is already being
used by the module
Flashing
red/green
Power up, self test
Flashing
red/green
Power up, self test
Link
(Green LED)
Activity
(Yellow LED)
Meaning
OFF
OFF
•
Module not ready, no control voltage.
•
No bus connection (check cable connection)
ON
OFF
•
Bus connection (cable connection) to another Ethernet device available
•
No bus activity available
ON
Flashing
(Blinking)
•
Bus connection (cable connection) to another Ethernet device available
•
Bus activity available
Pos : 21 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/ LED Anz eigen- N ORD s pezifisc he LED [EI P / PO L / ECT / PNT Allgemei n] @ 3\ mod_1363773424248_388. doc x @ 61815 @ @ 1
NORD-specific LEDs
DS
(Device status)
DE
(Device error)
Meaning
Long flash
= 0.5 s on / 1 s off
Short flash
= 0.25 s on / 1 s off
OFF
OFF
Module not ready, no control voltage.
ON
OFF
Module ready, no error, at least one frequency inverter is communicating via the system bus
ON
Short flashing
Module ready, but
•
One or more of the connected frequency inverters has fault status
Long flashing
OFF
Module ready and at least one other participant is connected to the system bus, but
•
no frequency inverter connected to system bus (connection may be interrupted)
•
one or more system bus clients has address error
•
Software incompatible (module software and FI software do not match - update required)
Long flashing
Short flashing
Flash interval
1 x - 1s pause
System bus is in status "Bus Warning"
•
Communication on system bus disrupted
•
No other clients available on system bus
•
Module not inserted correctly or no connection to the system bus
•
Frequency inverter has no supply voltage
Long flashing
Short flashing
Flash interval
2 x - 1s pause
System bus is in status "Bus Off"
•
the system bus 24V power supply was interrupted during operation
Long flashing
Short flashing
Flash interval
3 x - 1s pause
System bus is in status "Bus Off"
•
No system bus 24V power supply
Long flashing
Short flashing
Flash interval
4 x - 1s pause
Module error
•
see parameter P170
OFF
Short flashing
Flash interval
1…7 - 1s pause
System error, internal program sequence interrupted
•
EMC interference (observe wiring guidelines!)
•
Module defective