Series 38R ••• Self-Acting Temperature Control Valves

Operation, Installation & Maintenance Manual

PRINCIPLES OF OPERATION OF THE REGULATOR

The W.E. Anderson Model 38R Temperature Regulator operates on the vapor pressure principle. The thermally
sensitive bulb of the instrument contains a fluid that creates a vapor which increases or decreases in pressure as the
sensing bulb temperature increases or decreases. This vapor pressure is transmitted hydraulically to the bellows
which, opposed by the adjusting (return) spring, actuates the valve controlling the flow in proportion to the sensed
temperature at the bulb. Raising or lowering the adjusting screw will change the compression of the spring against the
bellows, thus raising or lowering the control temperature. For the most sensitive operation a nominal range should be
selected that contains the desired control point in the upper 1/3 of the nominal range. The vapor pressure response is
greater per unit of temperature change in the upper portion of the nominal range. All W.E. Anderson temperature
regulators (with the exception of the Option 3 “Fail-Safe”) are equipped with an over-range feature which allows
the bulb to be heated 100°F above the nominal range without damaging the temperature sensing system.

Recommended Working Span

Single Seat Heating Va l ve s

Double Seat Heating Va l ve s

Single Seat Cooling Va l ve s

Double Seat Cooling Va l ve s

˚ F (˚C)

Dial Thermometer Range

R a n ge Code

Nominal Range

All 3-Way Va l ves ˚ F (˚C)

˚ F (˚C)

R01*

20° to 70°F (-7 to 21)

40° to 65°F (4 to 18)

N/A

30° to 115°F (-1 to 46)

R02*

40° to 90°F (5 to 32)

65° to 85°F (18 to 29)

N/A

50° to 140°F (10 to 60)

R03

30° to 115°F (-1 to 46)

85° to 110°F (29 to 43)

50° to 80°F (10 to 27)

30° to 115°F (-1 to 46)

R04

50° to 140°F (10 to 60)

110° to 135°F (43 to 57)

80° to 105°F (27 to 41)

50° to 140°F (10 to 60)

R05

75° to 165°F (24 to 74)

135° to 160°F (57 to 71)

105° to 130°F (41 to 54)

75° to 165°F (24 to 74)

R06

105° to 195°F (41 to 91)

160° to 190°F (71 to 88)

130° to 155°F (54 to 68)

105° to 195°F (41 to 91)

R07

125° to 215°F (52 to 102)

190° to 210°F (88 to 99)

155° to 180°F (68 to 82)

125° to 215°F (52 TO 102)

R09

155° to 250°F (68 to 121)

210° to 245°F (99 to 118)

180° to 215°F (82 to 102)

155° to 250°F (68 TO 121)

R10

200° to 280°F (93 to 138)

245° to 275°F (118 to 135)

215° to 245°F (102 to 118)

200° to 280°F (93 TO 138)

R11

225° to 315°F (107 to 157)

275° to 310°F (135 to 152)

245° to 280°F (118 to 138)

225° to 315°F (107 TO 157)

R12

255° to 370°F (124 to 188)

305° to 365°F (152 to 185)

275° to 335°F (135 to 168)

255° to 370°F (124 TO 188)

R13

295° to 420°F (146 to 216)

365° to 415°F (185 to 213)

335° to 385°F (168 to 196)

295° to 420°F (146 TO 216)

R14

310° to 440°F (154 to 227)

415° to 435°F (213 to 224)

385° to 405°F (196 to 207)

310° to 440°F (154 TO 227)

*Not recommended for single seated valves.

STANDARD RANGES

Option 3 Fail-Safe Actuators

R a n ge

Nominal Range

C o d e

and Recommended Working Span

R 8 1

40° to 65°F (4 to 18)

R82

55° to 80°F (18 to 29)

R83

65° to 90°F (18 to 32)

R84

80° to 110°F (27 to 43)

R85

90° to 115°F (32 to 46)

R86

110° to 140°F (43 to 60)

R89

140° to 175°F (60 to 79)

R90

170° to 195°F (77 to 91)

R91

190° to 210°F (88 to 91)

R92

205° to 225°F (96 to 107)

R93

215° to 250°F (102 to 121)

R94

230° to 265°F (110 to 129)

R95

245° to 280°F (118 to 138)

R96

270° to 300°F (132 to 149)