beautypg.com

Reversing the valve action, 1/2” – 2” valve sizes only – Dwyer 38R User Manual

Page 14

background image

Series 38R ••• Self-Acting Temperature Control Valves

Operation, Installation & Maintenance Manual

REVERSING THE VALVE ACTION

Page 14

Direct-Acting valves close with temperature increase and inward stem motion.
On a regulator these valves are used for HEATING.

Reverse-Acting valves close with temperature decrease and outward stem motion.
On a regulator these valves are used for COOLING.

1/2” through 2” Bronze Body valves use the same parts for both versions, and as such
can be changed from one form to the other in most any shop.

1/2” – 2” Valve Sizes Only

Figure 7

Figure 8

Figure 9

Stem moves in to body

to close assembly.