Series 38R ••• Self-Acting Temperature Control Valves

Operation, Installation & Maintenance Manual

3 WAY-REGULATORS – Installation & Maintenance

The Actuators on these regulators are identical to those previously described and the bulb installation is also
identical. These valves require three piping connections and can be used to diverge the flow to either of two
outlets, or to converge two inlets into one outlet. Port C is normally closed and Port B closes as temperature
increases. Port A is the common port and remains open.

G

LOWER

PORT

(B)

UPPER

PORT

(C)

COMMON

PORT

(A)

F

E

for Mixing or Diverting

MIXING

FLOW DIAGRAM

DIVERTING

FLOW DIAGRAM

TEMPERATURE COLD

MIXING:

Inlet pressures must be equal and check valves are recommended in inlets.

DIVERTING:

Outlet pressures must be close to equal to provide consistent pressure differential
both ways if partial flows must be maintained.

NOTES:

This valve not to be used for Steam or Temperatures over 350˚F.

1

/

2

” thru 2” sizes have union ends and 2

1

/

2

” thru 4” sizes have flanged ends.

TEMPERATURE SET-POINT

TEMPERATURE HOT

TEMPERATURE COLD

TEMPERATURE SET-POINT

TEMPERATURE HOT