Mtl7700 series shunt-diode safety barriers – Dwyer MTL7787 User Manual

Page 5

background image

1

INM7700-6 Jan 2010

MTL7700 Series

Shunt-diode safety barriers

INM7700-6

Jan 2010

Figure 1: MTL7700 Series shunt-diode safety barriers

1

OVERVIEW

This instruction manual contains all information needed to install,
maintain, fault-find and test MTL7700 Series shunt-diode safety
barriers.

Section 3 includes a checklist of essential safety factors that must
be considered when using MTL7700 Series barriers as intrinsically
safe (IS) interfaces between safe and hazardous areas.

Read section

3 before beginning installation. Users within the European
Community should also refer to the supplied MTL publication:

INA7700

MTL7700 Series
Instructions for Safe Use

It is assumed that all necessary system design, specification and
engineering factors have been taken into account BEFORE installation
work begins. To assist pre-planning, the following MTL publications
covering the theory, design, application, specifications and
certification of shunt-diode safety barriers are available:

AN9003

Application Note:

A user’s guide to

intrinsic safety

AN9007

Application Note:

A user’s guide to

MTL700 Series shunt-diode safety
barriers

MTL IS catalogue

The MTL IS catalogue includes detailed
specifications of all MTL7700 Series
barriers and accessories

IS certificates

Copies of Baseefa, FM and CSA IS
apparatus and system certificates for
MTL7700 Series barriers

If not supplied with the product, these publications are available
either from the company website (

www.mtl-inst.com) or on request

from your local MTL office.

2

DESCRIPTION

2.1

Introduction

MTL7700 Series ‘fourth-generation’ intrinsically safe shunt-diode
safety barriers are innovative successors to the MTL700 Series.

MTL7700 Series barriers are 1-, 2- or 3-channel devices that use
intrinsically safe explosion-protection techniques to pass electrical
signals between safe and hazardous areas, whilst limiting transferred
energy to a level that cannot ignite flammable atmospheres.

Connected in series with wiring entering any hazardous area on
process plant, MTL7700 Series barriers prevent explosions in all
normally occurring explosive atmospheres – including mixtures of air
with flammable gases, vapours, dusts and fibres – if a fault or faults
develop in the safe area.

2.2

MTL7700 Series – barrier ranges

The range is based on a choice of models which, between them,
cover virtually all applications – including the protection of
installations incorporating uncertified devices known as ‘simple
apparatus’ (eg, switches, thermocouples, resistive sensors, photocells
and LEDs) or separately certified ‘energy-storing’ or ‘voltage-
producing apparatus’ (eg, ac sensors, proximity detectors,
transmitters and current-to pneumatic (I/P) converters. Being
intrinsically safe, shunt-diode barriers enable maintenance work or
calibration to be carried out ‘live’ without additional precautions. To
simplify selection, several ‘key’ barriers (see table 1) are highlighted
as meeting the majority of process control requirements.

This manual is related to the following products: