beautypg.com

Dwyer MS2-M User Manual

Page 5

background image

appendix I: Setting Modbus

®

Communication Protocol address of Unit

The address assignment is determined by adding the values for each of the
switches that are in the ON position. The transmitter comes from the factory with all
of the dip switches, except position 1, in the ON position as shown in Figure 6
below. The address of the transmitter would be 127 as it would be
64+32+16+8+4+2+1=127. Another example would be if the address desired was
eight, the only dip switch position in the ON position would be position 5 as shown
in Figure 7 below. When power is applied to the transmitter, the LCD (if connected)
will display the current address for approximately 10 seconds. If the current
address is invalid, the LCD will display “A Err”.

appendix II: Modbus

®

Registers

Switch Position
address Value

2
64

3
32

4
16

5
8

6
4

7
2

8
1

1
128

ON

1

2

3

4

5

6

7

8

figure 6: address of Transmitter is 127

ON

1

2

3

4

5

6

7

A

8

figure 7: address of Transmitter is 8

Though the minimum possible address would be address 0
when all the dip switch positions were set to OFF, and the

maximum possible address would be address 255 when all of the dip switches were
set to ON, the transmitter only has valid address from 1 to 247. Any address outside
of this range will give an error code.

NOTICe

Register
0001

0002

0003-0004

0005-0006

0007-0008

0009-0010

0011-0012

0013-0014

0015-0016

0017-0018

0019

0020

0021-0022

8001-8006

8007-8012

8013-8018

8019-8024

Description
Pressure in
0.001 inches
of water
column
Pressure in
Pascal
Pressure in
inches of
water column
Pressure in
Pascal
Pressure in
mm of water
column
Pressure in
kilopascals
Velocity in feet
per minute
Velocity in
meters per
seconds
Flow in cubic
feet per
minute
Flow in cubic
meters per
second
Sensor Type

Pressure
Sensor
Operational
Pressure
Sensor Errors
Modbus

®

Application
Firmware
Version
Sensor
Application
Firmware
Version
Modbus

®

Application
Serial Number
Sensor
Application
Serial Number

Data
Type
Signed
16Bit integer

Signed
16Bit integer
Float

Float

Float

Float

Float

Float

Float

Float

Unsigned
16Bit integer

Unsigned
16Bit integer

Unsigned
32Bit integer
String

String

String

String

Value

0...3

0...1

0...2

32

-1

Range

0-None,
1-Hall,
2-Piezo,
3-Capcell
Operational-
Nonoperational

0...2

32

-1

Multi-address
Supported
Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

No

No

No

No