CHANGE UPPER RANGE VALUE

1. Access the menu by pressing the Zero+Span buttons.
2. Move to the next menu by pressing the Zero button until

the 1 TRIM message appears.

3. Press the Span button until the 2 SETUP message appears.
4. Press the Span button until the 21 Unit message appears.
5. Press the Zero button until the 22 U-RNG message appears.
6. Press the Span button until the Zero Adjustment

message appears.

CHANGE LOWER RANGE VALUE

1. Access the menu by pressing the Zero+Span buttons.
2. Move the to next menu by pressing the Zero button until

the 1 TRIM message appears.

3. Press the Span button until the 2 SETUP message appears.
4. Press the Span button until the 21 Unit message appears.
5. Press the Zero button until the 22 U-RNG message appears.
6. Press the Zero button until the 23 L-RNG message appears.
7. Press the Span button until the Change Lower Range

Value message appears.

CHANGE LCD MODE (Cyclic or Fixed Display)

1. Enter programming menu by pushing both (ZERO+SPAN)

button together for 5 seconds. Release buttons when LCD
displays Menu and display will automatically change to “1
TRIM” confirming access into programming menu.

2. Push (ZERO) button when “1 TRIM” message appears on

LCD. Release button when display changes to “2 SETUP”.

3. Push (Zero) button and release when display changes to

“3 LCD”.

4. To move into sub directory push (Span) button after “3 LCD”

message appears on display. Release button when 31 LCD-
MD message is displayed.

5. To enter this sub-menu, push (Span) button and release

when display changes to 311. Bottom line of display will

show current Mode setting e.g. NOR-RO, NOR-PVetc.

6. Push (Zero) button to cycle through available mode options

and select desired LCD rotation mode. Options are:
NOR-RO (rotate all PV, %, mA), NOR-PV (fixed PV),
NOR-% (fixed %), NOR-mA fixed,
ENG-RO, ENG-PV, ENG-% or ENG-mA

7. Push (Span) to save changes and EXIT programming mode.

DECIMAL PLACE

1. Access the menu by pressing the Zero+Span buttons.
2. Move to the next menu by pressing the Zero button until

the 1 TRIM message appears.

3. Press the Span button until the 2 SETUP message appears.
4. Press the Span button until the 3 LCD message appears.
5. Press the Span button until the 31 DEC-PL message

appears.

6. Press the Span button until the Decimal Place

message appears, the decimal place will appear on the
second line of the LCD as follows.

7. The first line on the LCD will display 0.0.

8. The Decimal Place can be changed by pressing the Zero

button. Save the setting by pressing the Span button
after the decimal place has been selected.

9. The set value will display the PV value and

Engineering value.

10. The LCD will display LCD_OV and the saved Unit when

the pressure is over or under a set value.

3.8 Commissioning on the Bench with HHT
The 3100 Pressure Transmitter can be commissioned using an HHT
before or after installation.

Connect an HHT (HART

®

HANDHELD Communicator) across

the COMM pins for HART

®

communication. The TEST pin

connections can be used for connecting a multimeter to measure the
output current directly from the transmitter. Since the 3100 is a two
wire loop powered transmitter, it requires an external loop power
supply (11.9V to 45VDC) to enable HART

®

communication. Any

HART

®

communication via HHT (or PC based configurator) requires

a minimum 250 ~ 550 (max) ohm loop resistance.

Display
AUTO

5-0
4-1
3-2
2-3
1-4

Explanation
Target value will be displayed
automatically
No decimal place
Display one decimal place
Display two decimal places
Display three decimal places
Display four decimal places

Max. Value
99999

99999
9999.9
999.99
99.999
9.9999

[Figure 3-5 Connecting the Transmitter to HHT]

Figure 3-4 Transmitter Zero/Span Configuration Buttons