Sp1h, Sp2h, Sp1l – Dwyer DH User Manual

Page 7: Sp2l, Setting set points and alarms, In. w.c.), Set point adjustment adjusting the digihelic, Sets the relay turn on point, and, Sets the relay turn off point, and

background image

6

SETTING SET POINTS AND ALARMS

The hot key provides direct access to the Set Point and Alarm MENU. The
Set Point and Alarm MENUS that are displayed are based upon the Control (CtrL)
SUB MENU.

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

Visible when

Visible when

Visible when

Visible when

Visible when

Visible when

mode =

mode =

mode =

mode =

mode =

mode =

CONTROL MODE

CONTROL MODE

CONTROL MODE

CONTROL MODE

CONTROL MODE

CONTROL MODE

SET POINT ADJUSTMENT

Adjusting the Digihelic

®

Controller Set Points is quick and simple. Instead of setting

a set point and deadband, simply adjust

SP1H

or

SP2H

for the desired relay turn

on point, and then adjust

SP1L

or

SP2L

for the desired relay turn off point.

PRESSURE

PRESSURE

0

0

TIME

TIME

0.2

0.2

0.4

0.4

0.6

0.6

0.8

0.8

1.0

(in. w.c.)

In the above graph, an instrument with a 1.0˝ range would have the SP1 relay turn

on at 0.8˝ and off at 0.4˝.

SP1H

sets the relay turn on point, and

SP1L

sets the relay

turn off point. The relays outputs normally function in the direct acting mode, which
means the relays turn on with an increase in pressure. SP1 may be configured to act
as a reverse acting relay (refer to the 1SP SUB MENU setting, page 15). When set

for reverse acting,

SP1H

sets the relay turn OFF point, and

SP1L

sets the relay turn

ON point. SP2 is always direct acting.

SP/AL

SP/AL

B-32:B-32 7/9/09 2:52 PM Page 7