Blue Angel Pumps BCP20ULS User Manual
Condensate unit, Specifications, Description
Specifications
Power supply
requirements . . . . . . . . . .120V, 60 Hz,
1 phase
Motor duty . . . . . . . . . . .Intermittent
Liquid temperature
range . . . . . . . . . . . . . . . .40°F to 125°F
Max. operating
position . . . . . . . . . . . . . .45
o
from
vertical
Dimensions . . . . . . . . . . .10” X 5” X
4-3/4”
Discharge . . . . . . . . . . . . .3/8"ID
Power cord . . . . . . . . . . .6'
3 conductor
with ground
Reservoir . . . . . . . . . . . . .2 quart
plastic
Description
A condensate unit removes
condensation from air conditioning
and high efficiency furnaces. The
compact design of the unit consists of a
3/8” ID discharge and 6 ft. long power
cord. The unit also contains a safety
switch to automatically shut off pump
in the event of a failure.
Unpacking
Inspect this unit before it is installed.
Occasionally, products are damaged
during shipment. If the pump or
components are damaged, return the
unit to the place of purchase for
replacement. Failure to do so could
result in serious injury or death.
This pump is not
designed to handle
salt water, brine, laundry discharge, or
any other application which may contain
caustic chemicals and/or foreign
materials. Pump damage could occur if
used in these applications and will void
warranty. Use for clear water application
only.
Performance
Operating Instructions and Parts Manual
Model BCP20ULS
370103-002 1/07
Safety Guidelines
This manual contains information that
is very important to know and
understand. This information is
provided for SAFETY and to PREVENT
EQUIPMENT PROBLEMS. To help
recognize this information, observe the
following symbols.
Danger indicates
an imminently
hazardous situation which, if not
avoided, will result in death or serious
injury.
Warning indicates
a potentially
hazardous situation which, if not
avoided, could result in death or serious
injury.
Caution indicates a
potentially
hazardous situation which, if not
avoided, MAY result in minor or
moderate injury.
© 2007 Blue Angel ™ Pumps
Condensate Unit
GALLONS PER HOUR
AT TOTAL HEAD IN FEET
Head (ft)
2
6
8
10
19
Flow (GPH) 78 72 66 59
0
For parts, product & service information
visit www.blueangelpumps.com
REMINDER: Keep your dated proof of purchase for warranty purposes! Attach it to this manual or file it for safekeeping.
Figure 1 - Performance Chart
Please read and save these instructions. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by
observing all safety information. Failure to comply with instructions could result in
personal injury and/or property damage! Retain instructions for future reference.