Electrical classification
1) 2)
See Certificate of Conformity EX EVE0107A
Type of protection ATEX “intrinsically safe”
Analog positioner (Basic device)
Type AI 636 . . . . . . . . . . . . . II 2 G EEx ib/ia IIB/IIC T4/T6
Certificate of Conformity. . . . PTB 02 ATEX 2206
For use in hazardous areas in circuits certified as
intrinsically safe with the following maximum values:
Input circuit
U
i
. . . . . . . . . . . . . . . . . . . 30 V
I
i
. . . . . . . . . . . . . . . . . . . 130 mA
P
i
. . . . . . . . . . . . . . . . . . . 0.9 W
Internal inductance L
i
. . . . 25 μH
Internal capacitance C
i
. . . 18.9 nF diff. / 22.7 nF to earth
T6 Ambient temperature . . –40 ... 40 °C (–40 ... 104 °F)
T4 Ambient temperature . . –40 ... 80 °C (–40 ... 176 °F)
The control circuit is safely electrically isolated from ground
and all other circuits.
Additional equipment “Inductive limit switch”
For use in hazardous areas in circuits certified as intrinsi-
cally safe with the following maximum values:
U
max
. . . . . . . . . . . . . . . . . 16 V
I
max
. . . . . . . . . . . . . . . . . . 25 mA
P
max
. . . . . . . . . . . . . . . . . 64 mW
Internal inductance . . . . . . 100 μH
Internal capacitance . . . . . 30 nF
T6 Ambient temperature . . –40 ... 40 °C (–40 ... 104 °F)
T4 Ambient temperature . . –40 ... 80 °C (–40 ... 176 °F)
Permissible temperature class and ambient temperature
dependent on the basic device.
Additional equipment “Position Transmitter”
For use in hazardous areas in circuits certified as intrinsi-
cally safe with the following maximum values:
U
i
= 30 V, I
i
= 130 mA, P
i
= 0.9 W
Internal inductance L
i
. . . . 25 μH
Internal capacitance C
i
. . . 17.2 nF diff. / 21 nF to earth
The control circuit is safely electrically isolated from ground
and all other circuits.
Explosion protection Zone 2
It is recommended to use the positioner with explosion prot-
tection "intrinsically safe" acc. to EN 50020 an EN 50014
(consider temperature class). In the EU these positioner
may be operated in Zone 2 with non-intrinsically safe
circuits if the operating values do not exceed the maximum
reference values. The non intrinsic safe circuits has
additionally fulfill the requirements of EN61010-1 (IEC 1010-1),
protection grade III, overvoltage category I (transient voltage
lower than 40 %).
1) With appropriate order only
2) National requirements must be observed
Explosion protection Zone 20
Certificate of Conformity . . . . . . . . . IBExU08 ATEX 1148
EX II 1D Ex iaD 20 T 100°C –40 °C < T
a
< +80 °C
Electrical Data
Supply circuit in type of protection Intrinsic safety Ex ia or
Ex ib
Ui . . . . . . . . . . . . . . . . . 40 V DC
Ii . . . . . . . . . . . . . . . . . . 150 mA
Pi . . . . . . . . . . . . . . . . . 1000 mW
effective inner capacity Ci. . . 6 nF
effective inner inductivity Li . 5 μH
The supply connections have an inner capacity of max. 11 nF
opposite the ground.
The positioner type SRI990 fulfils the requirements of
explosion protection for the Equipment Group II and
Category 1D in type of protection Intrinsic safety for dust
with a maximum surface temperature of 100 °C.
With Electrical Classification ATEX + Zone 20 Dust, Codes
ED4 and EDA, the Travel indicator is not visible.
Type of protection
FM approved for “non-incendive”
Class I, II, III, Division 1, Groups A, B, C, D / T4,
hazardous locations, indoors and outdoors, NEMA 4X
FM approved for “intrinsic safety”
Class I, Division 1, Groups A, B, C, D, E, F, G / T4,
hazardous locations, indoors and outdoors, NEMA 4X
Functional Specifications Common to All Versions