General Description
STANDARD FEATURES
All models sizes.
Condenser
Large surface area coil(s) ideally positioned to optimise airflow and heat transfer,
manufactured from refrigeration quality copper tubes with mechanically bonded
aluminium fins.
Condenser Fan
Axial fan assemblies with fingerproof grille and incorporating external rotor motor
technology, to provide highly accurate discreet speed control, discharge air vertically. The
fans offer maximum performance while keeping sound levels to a minimum.
Electrical supply dependent upon model size, refer to
Head Pressure Control
Electronic head pressure controllers are fitted which modulate the fan speed to maintain
a constant condensing pressure, allowing the system to operate satisfactorily in ambient
temperatures as low as -20°C.
Head pressure can be set, monitored and values viewed at the microprocessor display.
Compressor
Scroll compressors comprising:
Internal motor protection
Internal pressure relief
Non return valve
External discharge temperature protection
Oil sight glass
Sump heater
Each Tandem / Trio set has an oil equalisation line.
The compressors are mounted to the rigid galvanised heavy duty sub-frame with the use
of vibration reducing isolation.
Refrigeration
Each refrigeration circuit is supplied with the following:
Holding charge of Helium
Liquid line ball valve
Suction line ball valve
Low pressure cut-out with manual reset via microprocessor controller
High pressure switch with manual reset
Pressure relief valve with integral rupture disc and indicator gauge
Refer to
for further detail.
Controls
microprocessor controller can provide 2-6 stages of capacity control,
dependent upon model type, as standard. The controller incorporates full Building
Management System capabilities, full details can be found in the
Control management is offered in 1 of 4 of the most common types, to select via the
microprocessor, to be specified at time of order:
External 0-10V Signal
Suction Pressure Monitoring
Remote Space Temperature Sensor
Remote Digital Inputs
Electrical
Dedicated weatherproof electrical power and controls panels are situated at the end of
the unit and contain:
Separate, fully accessible, controls compartment, allowing adjustment of control set
points whilst the unit is operational
Circuit breakers for protection of all major unit components
Separate, permanent supply for controls/trace heating, 230V/50Hz/1ph
The electrical power and control panel is wired to the latest European standards and
codes of practice.
UCCU75, 100-450
Mains supply is 3 phase and a neutral is not required. Refer to