Performance Data
SOUND DATA
Global Sound Level
Standard - D Models
Sound
Measurement
Overall
dB(A)
Frequency (Hz) dB
63
125
250
500
1000
2000
4000
Power
NOT APPLICABLE
Pressure
@ 10m
Power
Pressure
@ 10m
Power
Pressure
@ 10m
Power
Pressure
@ 10m
Power
Pressure
@ 10m
UCCU75D-2/1
Power
81
74
80
77
79
78
72
63
Pressure
@ 10m
49
42
48
45
47
46
40
31
Power
NOT APPLICABLE
Pressure
@ 10m
UCCU100D-2/1
Power
81
80
84
78
79
78
72
63
Pressure
@ 10m
49
48
52
46
47
46
40
31
UCCU110D-4/2
Power
88
82
89
82
82
84
82
77
Pressure
@ 10m
56
50
57
50
50
52
50
45
UCCU125D-3/1
Power
84
74
84
83
81
80
74
65
Pressure
@ 10m
52
42
52
51
49
48
42
33
UCCU130D-4/2
Power
88
79
89
84
82
84
82
77
Pressure
@ 10m
56
47
57
52
50
52
50
45
UCCU150D-3/1
Power
84
74
84
83
81
80
74
65
Pressure
@ 10m
52
42
52
51
49
48
42
33
UCCU160D-4/2
Power
88
79
89
84
82
84
82
77
Pressure
@ 10m
56
47
57
52
50
52
50
45
UCCU180D-6/2
Power
90
83
92
86
84
86
84
79
Pressure
@ 10m
58
51
60
54
52
54
52
47
UCCU200D-6/2
Power
90
81
91
87
84
86
84
79
Pressure
@ 10m
58
49
59
55
52
54
52
47
UCCU225D-6/2
Power
90
81
91
87
84
86
84
79
Pressure
@ 10m
58
49
59
55
52
54
52
47
UCCU250D-6/2
Power
90
81
91
87
84
86
84
79
Pressure
@ 10m
58
49
59
55
52
54
52
47
UCCU275D-8/2
Power
89
78
85
83
88
85
81
75
Pressure
@ 10m
57
46
53
51
56
53
49
43
UCCU300D-8/2
Power
89
78
85
83
88
85
81
75
Pressure
@ 10m
57
46
53
51
56
53
49
43
UCCU330D-10/2
Power
90
77
86
84
88
86
80
73
Pressure
@ 10m
58
45
54
52
56
54
48
41
UCCU360D-10/2
Power
90
75
86
84
89
86
80
73
Pressure
@ 10m
58
43
54
52
57
54
48
41
UCCU400D-12/2
Power
91
76
87
85
89
87
81
73
Pressure
@ 10m
59
44
55
53
57
55
49
41
UCCU450D-12/2
Power
91
76
87
85
90
87
81
74
Pressure
@ 10m
59
44
55
53
58
55
49
42
1
dB(A) is the overall sound level, measured on the A scale.
2
All sound data measured at nominal conditions: 5°C Evaporating temperature and 30°C ambient.
The Sound Pressure data quoted is only valid in free field conditions, where the unit is installed on a reflective base. If
the equipment is placed adjacent to a reflective wall, values may vary to those stated, typically increasing by 3dB for
each side added.