Ultima compact condensing units, General specification, Condensers & condensing units – Airedale Ultima Compact Condensing Unit 30kW - 450kW User Manual
Page 24: Electrical data
![background image](/manuals/370965/24/background.png)
ULTIMA COMPACT
Condensing Units
24
Condensers & Condensing Units
Technical Manual : Part No 904-047 V1.4.0_02_2013
General Specification
ELECTRICAL DATA
UCCU160D-4/2
UCCU180D-6/2
UCCU200D-6/2
UCCU225D-6/2
UCCU250D-6/2
UCCU275D-8/2
Unit Data
Nominal Run Amps
(1) A
115
132
146
158
172
160
Maximum Start Amps
(2) A
264
315
377
389
403
440
Permanent Supply
VAC
230 V 1 PH 50 Hz
Mains Supply
VAC
400 V 3 PH 50 Hz
Rec Permanent Fuse Size
A
16
16
16
16
16
16
Rec Mains Fuse Size
A
125
160
160
200
200
200
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Control Circuit
VAC
24V/230V AC
Condenser Fan - Per Fan
Quantity
4
6
6
6
6
8
Full Load Amps
A
2.70
2.70
2.70
2.70
2.70
1.75
Locked Rotor Amps
A
7.00
7.00
7.00
7.00
7.00
6.20
Motor Rating
kW
1.60
1.60
1.60
1.60
1.60
0.98
Compressor - Per Compressor
Quantity
4
2 + 2
2 + 2
2 + 2
4
2 + 2
Motor Rating
kW
11.7
15.0 / 11.7
18.2 / 11.7
18.2 / 15.0
18.2
22.8 / 18.2
Nominal Run Amps
(1) A
26.0
32.0 / 26.0
39.0 / 26.0
39.0 / 32.0
39.0
47.0 / 39.0
Sump Heater Rating
W
75.0
130.0 / 75.0
130.0 / 75.0
130.0 / 130.0
130.0
130.0 / 130.0
Start Amps
(2)
175.0
215.0 / 175.0
270.0 / 175.0
270.0 / 215.0
270.0
320.0 / 270.0
Type Of Start
Direct on line
QUIET DQ
UCCU160DQ-6/2
UCCU180DQ-6/2
UCCU200DQ-6/2
UCCU225DQ-8/2
UCCU250DQ-8/2
UCCU275DQ-10/2
All data as above except:
Condenser Fan - Per Fan
Quantity
6
6
6
8
8
10
Full Load Amps
A
1.25
1.25
1.25
1.25
1.25
1.15
Locked Rotor Amps
A
4.50
4.50
4.50
4.50
4.50
2.10
Motor Rating
kW
0.69
0.69
0.69
0.69
0.69
0.70
SUPER QUIET DSQ
UCCU160DSQ-6/2
UCCU180DSQ-6/2
UCCU200DSQ-8/2
UCCU225DSQ-8/2
UCCU250DSQ-8/2 UCCU275DSQ-12/2
All data as above except:
Condenser Fan - Per Fan
Quantity
6
6
8
8
8
12
Full Load Amps
A
0.78
0.78
0.78
0.78
0.78
0.83
Locked Rotor Amps
A
1.50
1.50
1.50
1.50
1.50
1.50
Motor Rating
kW
0.48
0.48
0.48
0.48
0.48
0.32
OPTIONAL EXTRAS
Power Factor Correction
Nominal Run Amps
(1) A
103
118
132
142
156
146
Maximum Start Amps
(2) A
264
315
377
389
403
430
Recommended Mains Fuse
A
125
125
160
160
200
200
Compressor Nominal Run Amps
- Per Compressor
A
4 x 20
2 x 24 / 2 x 20
2 x 30 / 2 x 20
2 x 30 / 2 x 24
4 x 30
2 x 36 / 2 x 30
Electronic Soft-start
Nominal Run Amps
(1) A
115
132
146
158
172
160
Maximum Start Amps
(2) A
194
229
269
281
295
302
Recommended Mains Fuse
A
125
160
160
200
200
200
(1)
Based at 7.2°C Evaporating and 54.4°C Condensing temperatures.
(2)
Starting amps refers to the direct on line connections.