Chillers ultima compact freecool, General description – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 9
Chillers
ULTIMA COMPACT FREECOOL
Chillers
9
Technical Manual : 6259576 V1.2.0_02__2013
General Description
STANDARD FEATURES
Refrigeration
Each refrigeration circuit is supplied with the following:
Full operating charge of R407C
Electronic Expansion Valve (EEV)
Liquid line ball valve
Discharge line ball valve
Large capacity filter drier with replaceable cores
Liquid line sight glass
Low pressure switch with manual reset via microprocessor controller
High pressure switch with manual reset
Suction and liquid pressure transducers
Valves for refrigeration head pressure control
Compressor minimum differential pressure protection
Pressure relief valve with integral rupture disc and indicator gauge URAC180
– 450,
(Optional to UCFC75
– 160)
Water / Glycol
Each water glycol circuit is supplied with the following:
Water Flow switch
3 way modulating valve to control free cooling operation
Strategically placed automatic air vents
Strategically placed drain valves
Butterfly shut off valve for free cooling coil isolation to allow for maintenance
Pressure transducers across evaporator to monitor water pressure drop
Inlet water filter 20 mesh
Controls
As standard, the
microprocessor controller can provide 2, 4 or 6 stages of
capacity control, dependent upon model type.
Optionally, the controller is designed to provide capabilities for;
Building Management Systems
Networking
Sequencing (Master/Slave and Run/Standby)
to meet all your system requirements, please specify at order.