Temperature control, Chillers ultima compact freecool, Controls – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 17
![background image](/manuals/370944/17/background.png)
Chillers
ULTIMA COMPACT FREECOOL
Chillers
17
Technical Manual : 6259576 V1.2.0_02__2013
Controls
TEMPERATURE
CONTROL
Airedale recognises that all chiller applications are different but fall mainly into 2
application categories; Variable Supply Temperature and Constant Supply Temperature.
The onboard microprocessor has the capability of satisfying either control requirement as
illustrated below.
Using the Airedale Variable Supply Temperature control scheme,
energy savings are available when compared with previous schemes and that of the
Constant Supply Temperature application.
Variable Supply Temperature control schemes offer energy savings where the supply
water temperature is not critical to its operation and is recommended for free
cooling applications.
Selection of the best application control scheme can be made via a soft switch in the
microprocessor during initial commissioning.
The microprocessor maintains the set supply Chilled Water temperature by sensing the
return and supply water temperatures and ambient air temperature to adjust the
compressor loading and water valve position as required.
Examples based on Models UCFC125D-3/1 having 6 Stages of Cooling
Key:
1
Return Water Temperature
2
Mean Value
3
Supply Water Temperature
4
Compressor Off
Variable Supply
Temperature Control
Wa
te
r Te
m
pe
ratu
re
°C
6
7
8
9
10
11
12
13
14
1
3
4
2
17% / 1
34% / 2
50% / 3
67% / 4
94% / 5
100% / 6
Chiller Capacity % / Cooling Stage Sequence
Constant Supply
Temperature Control
Wa
te
r Te
m
pe
ratu
re
°C
6
7
8
9
10
11
12
13
14
17% / 1
34% / 2
50% / 3
67% / 4
94% / 5
100% / 6
1
3
Chiller Capacity % / Cooling Stage Sequence
CAUTION
Factory set to Variable Supply Temperature Control unless otherwise stated
at order.
Only when the mode selection has been set can the unit be enabled.