Electrical data, Ultima compact freecool chillers, General specification – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 46: Chillers
![background image](/manuals/370944/46/background.png)
ULTIMA COMPACT FREECOOL
Chillers
46
Chillers
Technical Manual : 6259576 V1.2.0_02__2013
General Specification
ELECTRICAL DATA
UCFC75D-2/1
UCFC100D-2/1
UCFC125D-3/1
UCFC150D-3/1
UCFC160D-6/2
Unit Data
(1)
Nominal Run Amps
A
50
62
79
93
99
Maximum Start Amps
A
140
167
217
246
252
Rec Mains Fuse Size
A
63
80
125
125
125
Mains Supply
VAC
400V / 3PH / 50 Hz
Max Mains Incoming Cable Size
mm²
70 (direct to
MCCB)
70 (direct to
MCCB)
70 (direct to
MCCB)
70 (direct to
MCCB)
Direct to Bus Bar
Permanent Supply
VAC
230V / 1PH + N / 50 Hz
Rec Permanent Fuse Size
A
16
16
16
16
16
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Immersion Heater Rating
W
40
40
80
80
100
External Trace Heating
Available (fitted by others)
W
500
500
500
500
500
Fan & Motor - Per Fan
Quantity
2
2
3
3
6
Full Load Amps
A
1.75
1.75
1.75
1.75
1.75
Locked Rotor Amps
A
6.20
6.20
6.20
6.20
6.20
Motor Size
kW
0.98
0.98
0.98
0.98
0.98
Compressor - Per
Compressor
(1)
Quantity
4
4
2 + 2
4
4
Motor Size
kW
6.2
8.1
8.1 / 11.7
11.7
11.7
Nominal Run Amps
A
11.7
14.6
14.6 / 22.0
22.0
22.0
Oil Heater Rating
W
65.0
65.0
65.0 / 75.0
75.0
75.0
Start Amps
(2)
A
98.0
120.0
120.0 / 175.0
175.0
175.0
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
(1)
Nominal Run Amps
A
48
55
71
85
91
Maximum Start Amps
(2)
A
140
167
217
246
252
Recommended Mains Fuse
A
63
80
125
125
125
Compressor Nominal Run
Amps - Per Compressor
A
4 x 11
4 x 13
2 x 20 / 2 x 13
4 x 20
4 x 20
Electronic Soft-Start
(1)
Nominal Run Amps
A
50
62
79
93
99
Maximum Start Amps
(2)
A
97
119
147
176
182
Recommended Mains Fuse
A
63
80
125
125
125
Water Pump
(1)
Single Head or Run/Standby
- Standard
Unit Nominal Run Amps
A
55
67
86
98
113
Recommended Mains Fuse
A
80
100
125
125
160
Motor Size
kW
2.2
2.2
3.0
3.0
7.5
Full Load Amps
A
4.8
4.8
6.8
6.8
14.7
Single Head or Run/Standby
-Larger
Unit Nominal Run Amps
A
57
69
85
108
120
Recommended Mains Fuse
A
80
100
125
125
160
Motor Size
kW
3.0
3.0
7.5
7.5
11
Full Load Amps
A
6.8
6.8
15.5
15.5
21.4
Twin Head - Standard
Unit Nominal Run Amps
A
56
68
85
99
113
Recommended Mains Fuse
A
80
100
125
125
160
Motor Size
kW
3.0
3.0
3.0
3.0
7.5
Full Load Amps
A
6.1
6.1
6.1
6.1
14.7
Twin Head - Larger
Unit Nominal Run Amps
A
56
70
87
102
120
Recommended Mains Fuse
A
80
100
125
125
160
Motor Size
kW
3.0
4.0
4.0
4.0
11
Full Load Amps
A
6.1
7.7
7.7
7.7
21.4
(1)
Based at 12/7°C water and 30°C ambient with standard ac type fans.
(2)
Starting amps refers to the Star connection only with standard ac type fans.