POSITIONING
The installation position should be selected with the following points in mind:
Position on a stable and even base, levelled to ensure that the compressor
operates correctly
Levelling should be to +/- 5mm
Where vibration transmission to the building structure is possible, fit spring anti-
vibration mounts and flexible water connections
Observe airflow and maintenance clearances
Pipework and electrical connections are readily accessible
Where multiple units are installed, due care should be taken to avoid the discharge
air from each unit adversely affecting other units in the vicinity
Within a side enclosed installation, the fan MUST be higher than the
enclosing structure
Figures in brackets indicate airflow and maintenance clearances for side-enclosed or
multiple chiller applications
Ensure there are no obstructions directly above the fans
Allow free space above the fans to prevent air recirculation
CAUTION
Prior to connecting services, ensure that the equipment is installed and
completely level.
The Sound Pressure data quoted (refer to
, on page 37 ) is only valid in free
field conditions, where the unit is installed on a reflective base. If the equipment is placed
adjacent to a reflective wall, values may vary to those stated in our Performance Data
section, typically increasing by 3dB(A) for each side added.
Airflow & Maintenance
Clearances:
1 = 1.0m (2.0m)