WATERSIDE PRESSURE DROPS
(20% Ethylene Glycol Concentration)
CAUTION
Full design water flow MUST be maintained at all times. Variable water volume is
NOT recommended and will invalidate warranty.
Use the formula below to calculate the External Head Available:
Total Pump Head Available
-
Chiller Pressure Drop
=
External Head Available
Example: UCFC125D-3/1 6.12 l/s, standard single pump:
265 kPa
-
112 kPa
=
153 kPa