Water system, Standard recommended installation, Chillers ultima compact freecool – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 59: Installation data
Chillers
ULTIMA COMPACT FREECOOL
Chillers
59
Technical Manual : 6259576 V1.2.0_02__2013
Installation Data
WATER SYSTEM
Chilled water pipework and ancillary components must be installed in accordance with:
National and Local Water supply company standards
The manufacturer's instructions are followed when fitting ancillary components
The system water is treated to prevent corrosion and algae forming
Glycol required as standard, with the correction concentration to suit the lowest
ambient the equipment will experience
The schematic is referred to as a guide to ancillary recommendations
CAUTION
The unit water connections are NOT designed to support external pipework,
pipework should be supported separately.
STANDARD RECOMMENDED INSTALLATION
GENERAL
The following diagram illustrates the minimum component installation requirements. A
wide range of optional extras are available to suit various applications, please refer to
, on page 10 for details.
CAUTION
The following installation recommendations should be adhered to. Failure to do
this may invalidate the chiller warranty.
The water flow commissioning valve set is not shown in the diagram, as the valve can be
fitted elsewhere within the chilled water circuit.
T
T
FS
M
P
P
5
2
6
3
4
7
1
TT
M
P
P
2
1
3
4
4
1
Flushing By Pass Leg
2
Pump
3
Filter 1/16”
4
Pressure Sensor
CAUTION
Full design water flow MUST be maintained at all times. Variable water volume is
NOT recommended and will invalidate warranty.
CAUTION
The correct operation of the flow switch is critical if the chiller warranty is to
be valid.
CAUTION
Following components are fitted within the chiller unit as standard:
Temperature Sensors
Drain Point
Auto Air Vent
Flow Switch
20 Mesh Inlet Filter