Ultima compact freecool chillers, General specification, Chillers – Airedale Ultima Compact FreeCool 30kW - 450kW User Manual
Page 48: Electrical data
ULTIMA COMPACT FREECOOL
Chillers
48
Chillers
Technical Manual : 6259576 V1.2.0_02__2013
General Specification
ELECTRICAL DATA
UCFC180D-6/2
UCFC200D-6/2
UCFC225D-6/2
UCFC250D-8/2
UCFC275D-8/2
Unit Data
(1)
Nominal Run Amps
A
109
121
131
146
160
Maximum Start Amps
A
297
358
368
383
440
Rec Mains Fuse Size
A
160
160
200
200
200
Mains Supply
VAC
400V / 3PH / 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Permanent Supply
VAC
230V / 1PH + N / 50 Hz
Rec Permanent Fuse Size
A
16
16
16
16
16
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Immersion Heater Rating
W
100
100
100
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
500
500
Fan & Motor - Per Fan
Quantity
6
6
6
8
8
Full Load Amps
A
1.75
1.75
1.75
1.75
1.75
Locked Rotor Amps
A
6.20
6.20
6.20
6.20
6.20
Motor Size
kW
0.98
0.98
0.98
0.98
0.98
Compressor - Per
Compressor
(1)
Quantity
2 + 2
2 + 2
2 + 2
4
2 + 2
Motor Size
kW
15.0 / 11.7
18.2 / 11.7
18.2 / 15.0
18.2
22.8 / 18.2
Nominal Run Amps
A
27.0 / 22.0
33.0 / 22.0
33.0 / 27.0
33.0
40.0 / 33.0
Oil Heater Rating
W
130.0 / 75.0
130.0 / 75.0
130.0 / 130.0
130.0
130.0 / 130.0
Start Amps
(2)
A
215.0 / 175.0
270.0 / 175.0
270.0 / 215.0
270.0
320.0 / 270.0
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
(1)
Nominal Run Amps
A
99
111
119
134
146
Maximum Start Amps
(2)
A
290
351
359
374
430
Recommended Mains Fuse
A
125
160
160
200
200
Compressor Nominal Run
Amps - Per Compressor
A
2 x 24/2 x 20
2 x 30/2 x 20
2 x 30/2 x 24
4 x 30
2 x 36 / 2 x 30
Electronic Soft-Start
(1)
Nominal Run Amps
A
109
121
131
146
160
Maximum Start Amps
(2)
A
211
250
260
275
312
Recommended Mains Fuse
A
160
160
200
200
200
Water Pump
(1)
Single Head or Run/Standby
- Standard
Unit Nominal Run Amps
A
123
135
145
161
174
Recommended Mains Fuse
A
160
200
200
200
250
Motor Size
kW
7.5
7.5
7.5
7.5
7.5
Full Load Amps
A
14.7
14.7
14.7
14.7
14.7
Single Head or Run/Standby
-Larger
Unit Nominal Run Amps
A
130
142
152
167
181
Recommended Mains Fuse
A
160
200
200
200
250
Motor Size
kW
11
11
11
11
11
Full Load Amps
A
21.4
21.4
21.4
21.4
21.4
Twin Head - Standard
Unit Nominal Run Amps
A
123
135
145
161
174
Recommended Mains Fuse
A
160
200
200
200
250
Motor Size
kW
7.5
7.5
7.5
7.5
7.5
Full Load Amps
A
14.7
14.7
14.7
14.7
14.7
Twin Head - Larger
Unit Nominal Run Amps
A
130
142
152
167
181
Recommended Mains Fuse
A
160
200
200
200
250
Motor Size
kW
11
11
11
11
11
Full Load Amps
A
21.4
21.4
21.4
21.4
21.4
(1)
Based at 12/7°C water and 30°C ambient with standard ac type fans.
(2)
Starting amps refers to the Star connection only with standard ac type fans.