Multi-Temperature-Controller KS 800
4
Electrical connection
•
Measurement and signal leads may carry max. 50 V rms against earth.
•
Mains cables must be kept separate from signal and measurement cables.
•
For protection of the outputs and avoiding interference, connected final elements must be
fitted with protective circuits according to manufacturer specification.
4.1
Terminals
All terminals leading to the process are designed as (plug-in) screw terminals or spring clamps.
The terminals are not included in the scope of delivery and must be ordered separately.
Type: PHOENIX COMBICON
Two types are available:
Screw terminal
4 x FRONT-MSTB 2,5/18-ST-5,08
1 x FRONTMSTB 2,5/8-ST-5,08
PMA Order-No.
9407 799 00001
9407 799 00011
Spring clamp
4 x FK-MSTBP 1,5/18-ST-5,08
8-pole not suitable
PMA Order-No.
-----
-----
For units with analog outputs,
2 x 8-pole terminal, order no. 231-308/026-000, resp. 9407 799 00011
is required additionally.
Note: The screwless spring clamps are shown in the KS 800 figures. These clamps have a sepa-
rate test socket. With the screw terminals, the screw heads are used for test measurements.
Connecting capacity
FRONT-MTSB 2,5/...-ST
FK-MSTBP 1,5/...-ST
rigid
flexible
1
)
rigid
flexible
1
)
One wire [mm²]
0,2 - 2,5
0,25 - 2,5
0,2 - 1,5
0,25 - 1,5
Multiple-wire connection [mm²]
2
)
0,2 - 1,5
0,25 - 1,0
0,2 - 1,0
0,5 - 0,75
3
)
1
) with end crimps
2
) 2 wires of equal cross section
3
) with TWIN end crimps
Type : WAGO Multi-Connection-System MIDI
Spring-clamp
4 x female connector with CAGE CLAMP order no. 231-318/026-000
PMA Order-No.
9463 000 05341
1 x female connector with CAGE CLAMP order no. 231-308/026-000
PMA Order-No.
9463 000 05321
Connecting capacity
Only one wire: 0,08 - 2,5 mm², single-wire, multiple-wire, fine-wire, end crimp, pin cable shoe
9499 040 49111