West Control Solutions KS 800 Operating Instructions User Manual
Page 28

Multi-Temperature-Controller KS 800
8.2.3
COM2 interface
Address and Baudrate for the COM2 interface can be adjusted via hardware or software for each
KS 800.
Via hardware, the address is adjustable within ”01” and ”99”. In position ”00”, the address stored in
EEPROM which can be changed via software will be used when switching on. Priority is given to
the address adjusted via switch position. This address and baudrate cannot be readout or changed
via software.
The same applies to the Baudrate: in Position ”0”, the EEPROM Baudrate is effective at first. This
address can be changed via software. The digits on the switch correspond to the values used for
determination of the Baudrate during configuration in C902.
Switch position
RS485
CANbus
0
from EEPROM or via software
from EEPROM or via software
1
2400 Bd
20 kBd
2
4800 Bd
125 kBd
*
)
3
9600 Bd
500 kBd
*
)
4
19200 Bd
1 Mbd
5
invalid setting
10 kBd
6
invalid setting
50 kBd
7
invalid setting
250 kBd
*
)
8
invalid setting
800 kBd
9
invalid setting
invalid setting
As the baudrate is adjusted automatically with the PROFIBUS DP-version, manual adjustment is
omitted.
*
) Only these Baudrates are available for DeviceNet. With faulty switch position 125 kBd is set
automatically.