Multi-Temperature-Controller KS 800
8
Digital interfaces
Communication with controller KS 800 is possible only via the digital interfaces. Reading process
values, changing set-points or control parameters is always done via these interfaces.
There are two types of interfaces:
8.1
Engineering tool interface
The PC interface is provided on all controller versions. This interface is a special interface using the
ISO 1745 protocol. Access to all controller values is possible using the relevant software, the engi-
neering tool. E.g. for simple applications or test circuits, an individual unit can be configured and the
control loops can be operated normally via this interface.
Connection is to the 4/4 FCC68 data connector (Western telephone connector) via a special
PC adaptor, order no. 9407 998 00001.
8.2
BUS interfaces
This interface is used for connecting the KS 800 to a PLC, a PC or a visualization unit. Dependent
of version, the interface is designed for CANbus, CANbus with DeviceNet-protocoll, Profibus or as
RS 422/485 (see section 2.1). The 9-pole sub-D connector and socket are equivalent. They are
used for "through-connecting" the bus with several connected controllers.
See also page 8: Bus connectors
8.2.1
BUS-Connector
Con-
tact
Profibus
CANbus
RS422/485
DeviceNet
1
n.c.
n.c.
n.c.
See chapt. 8.2.2
"DeviceNet-Adaptor"
2
n.c
CAN-L
GND
3
n.c.RxD/TxD-P
CAN-GND
TXD-B
4
DGNC
n.c.
RXD-B
5
n.c.
n.c.
RGND
6
Vp(+5V)
CNA-GND
n.c.
7
n.c.
CAN-H
GND
8
RxD/TxD-N
n.c.
TXD-A
9
n.c
n.c.
RXD-A