Operating conditions, Performance under operating conditions, Environmental – West Control Solutions N8080 (for 2xxx) User Manual
Page 39: Physical
Operating Conditions
Ambient Temperature:
0
°
C to 55
°
C
Relative Humidity:
20% - 95% non-condensing
Performance Under Operating Conditions
Temperature Stability:
0.005% of span/
°
C change in ambient
temperature.
A.10
ENVIRONMENTAL
EMI Susceptibility:
Complies with EN50082-1:1992,
EN50082-1:1995.
NOTES:
1. For RF electromagnetic fields (10V/m 80% AM 1kHz), the reading
accuracy may be impaired by up to
−
0.3% in the frequency band
87 to 109MHz.
2. For line-conducted disturbances induced by RF fields (10V 80%
AM 1kHz), the product is self-recoverable in the frequency band
0.15 - 0.73MHz.
EMI Emmissions:
Complies with EN50081-1:1992,
EN50081-2:1993.
Safety:
Complies with EN61010-1.1993.
Supply Voltage:
90 - 264V, 50/60Hz (standard)
20 - 50V AC/DC (option)
Power Consumption:
4watts approximately
Front Panel Sealing:
To IP66 (Nema 4)
A.11
PHYSICAL
Dimensions:
Height - 48mm
Width - 96mm
Depth - 100mm
Mounting:
Panel-mount; press-fit fixing strap supplied.
Panel cut-out - 45mm x 92mm
Terminals:
Screw type; combination head.
Weight:
0.21kg maximum.
PM091-A
Volume II
A-4
59136